1. Comparisons of HVAC Simulations Between EnergyPlus and DOE-2.2 for Data Centers.
- Author
-
Tianzhen Hong, Mathew, Paul, Sartor, Dale, and Yazdanian, Mehry
- Subjects
- *
HEATING & ventilation industry , *COOLING , *ENERGY consumption , *DATA libraries , *ALGORITHMS - Abstract
This paper compares HVAC simulations between EnergyPlus and DOE-2.2 for data centers. The HVAC systems studied in the paper are packaged direct expansion air-cooled single zone systems with and without air economizer. Four climate zones are chosen for the study - San Francisco, Miami, Chicago, and Phoenix. EnergyPlus version 2.1 and DOE-2.2 version 45 are used in the annual energy simulations. The annual cooling electric consumption calculated by Energy- Plus and DOE-2.2 are reasonably matched within a range of -0.4% to 8.6%. The paper also discusses sources of differences between EnergyPlus and DOE-2.2 runs including cooling coil algorithm, performance curves, and important energy model inputs. [ABSTRACT FROM AUTHOR]
- Published
- 2009