1. Observation of Lightning at 500kV Transmission Lines (Part 1)
- Author
-
Ozawa Akio, Masaki Nakada, Takehiko Kikuchi, Katsuhiro Ouchi, and Yoshihisa Tamura
- Subjects
Meteorology ,Energy Engineering and Power Technology ,Lightning ,Electric power transmission ,Shielding Failure ,Transmission line ,Waveform ,Distribution of lightning ,Electrical and Electronic Engineering ,Tower ,Seismology ,Geology ,Transmission tower ,Remote sensing - Abstract
We investigated the phenomenon of lightning strokes on 500-kV transmission lines from 1984 to 1993. The investigation covered the recording of lightning paths by still cameras and measurements of lightning current at the lower part of transmission tower on 31 towers, over a 12.7-km-long section of the transmission line. We also observed lightning on an isolated tower at a nuclear power station. In the course of lightning observations spanning a 10-year period, we have confirmed the suitability of the lightning protection design on transmission lines. The distribution of lightning incidence angle (θ) expressed in terms of (cosmθ) was characterized by exponent m = 2 for the three-dimensional observations and m = 3.5 for the two-dimensional observations. No cases of shielding failure on 500-kV transmission lines were observed. The ratio of lightning current at the top of the isolated tower to the lower part was about 11 to 1. In addition, the lightning current waveform at the top of the isolated tower was similar to that at the lower part. © 1999 Scripta Technica, Electr Eng Jpn, 130(2): 59–67, 2000
- Published
- 1997
- Full Text