1. Final design of the Korean AC/DC converters for the ITER coil power supply system.
- Author
-
Oh, Jong-Seok, Choi, Jungwan, Suh, Jae-Hak, Choi, Jihyun, Lee, Lacksang, Kim, Changwoo, Park, Hyungjin, Jo, Seongman, Lee, Seungyun, Hwang, Kwangcheol, Liu, Hyoyol, Hong, Ki-Don, Sim, Dong-Joon, Lee, Jang-Soo, Lee, Eui-Jae, Kwon, Yang-Hae, Lee, Dae-Yeol, Ko, Ki-Won, Kim, Jong-Min, and Song, Inho
- Subjects
- *
ALTERNATING current electric motors , *DIRECT currents , *POWER resources , *THYRISTORS , *ACCURACY - Abstract
The final design of the ITER TF, CS, CC and VS AC/DC converters has been completed to implement ITER requirements following the detailed design and refinements of the preliminary design. The number of parallel thyristors and the rating of fuses are coordinated to keep those devices within the explosion limit even under most severe fault conditions. The impedance of the converter transformer has been optimized taking into account the energization inrush current, short circuit current, reactive power consumption and the available DC voltage. To ensure system integrity, AC/DC converters are mechanically divided into transformers, AC busbars, 6-pulse bridges, DC interconnecting busbars and DC reactors, and then all subsystems are decoupled by flexible links. To provide stable real time network communication down to the converters, a one GbE link is deployed between master controllers and local controllers. IEEE 1588 is implemented to the embedded controllers for precision time synchronization. This paper describes the detailed solutions implemented in the final design for the ITER AC/DC converters with R&D results of converter prototypes. [ABSTRACT FROM AUTHOR]
- Published
- 2015
- Full Text
- View/download PDF