1. The effect of Applied-voltage on photon-number of corona discharge on transmission lines defect
- Author
-
Chen Lan, Guo Xinyang, Zhao Xuesong, Bian Xingming, Guan Zhicheng, Yao Wenjun, Wan Shuwei, Wang Liming, and Mark MacAlpine
- Subjects
endocrine system ,Materials science ,business.industry ,medicine.disease_cause ,Corona ,Electric power transmission ,Electric field ,Partial discharge ,medicine ,Corona ring ,Optoelectronics ,Electric discharge ,Atomic physics ,business ,Ultraviolet ,Corona discharge - Abstract
Defects of high-voltage transmission lines are often accompanied with corona discharge; and corona discharge would produce ultraviolet. Based on this principle, the UV imager can be used in detecting the defect. Electric field strength is the main factor affecting the corona discharge, which is determined by power-supply and experimental model. In this paper, UV measurement of different defects was studied, and the effect of Applied-voltage on corona discharge of defects was acquired. A quadratic relationship exists between the UV strength produced by corona discharge and applied voltage. The quadratic coefficient A is between 0.31~0.37, which is increase with the length increasing at the experimental conditions in this paper.
- Published
- 2013
- Full Text
- View/download PDF