42 results on '"Zero-Sequence"'
Search Results
2. 零序非工频分量注入式微电网接地故障保护方案.
- Author
-
赵怀健, \牟龙华, and 方重凯
- Subjects
MICROGRIDS ,TOPOLOGY - Abstract
Copyright of Electric Power Automation Equipment / Dianli Zidonghua Shebei is the property of Electric Power Automation Equipment Press and its content may not be copied or emailed to multiple sites or posted to a listserv without the copyright holder's express written permission. However, users may print, download, or email articles for individual use. This abstract may be abridged. No warranty is given about the accuracy of the copy. Users should refer to the original published version of the material for the full abstract. (Copyright applies to all Abstracts.)
- Published
- 2022
- Full Text
- View/download PDF
3. Impedance Modeling and Stability Analysis of Three-Phase Four-Leg Grid-Connected Inverter Considering Zero-Sequence
- Author
-
Heng Nian, Yuming Liao, Meng Li, Dan Sun, Yunyang Xu, and Bin Hu
- Subjects
Impedance modeling ,three-phase four-leg grid-connected inverter ,zero-sequence ,stability analysis ,Electrical engineering. Electronics. Nuclear engineering ,TK1-9971 - Abstract
With the increasing applications of grid-connected voltage source converters, it is important to analyze the impedance characteristic of the grid-connected system to implement the stability analysis of the grid connection operation. Compared with the three-phase three-wire system, an additional zero-sequence path exists in the three-phase four-wire system. Therefore, it is necessary to consider the influence of the zero sequence when analyzing the stability of the system. In this paper, an impedance model including positive-sequence, negative-sequence and zero-sequence impedance of the three-phase four-leg grid-connected inverter is established. Through impedance characteristic analysis, the relationships between zero-sequence impedance and positive-sequence, negative-sequence impedance can be found which are decupled. Based on the developed zero-sequence impedance model, the main factors affecting the zero-sequence impedance model are revealed. Then, the system stability consisting of the grid and three-phase four-wire inverter is investigated, and the experimental results validate the theoretical analysis.
- Published
- 2021
- Full Text
- View/download PDF
4. An Analytical Zero Sequence Method to Locate Fault in Distribution Systems Rich in DG.
- Author
-
Penido, Debora Rosana Ribeiro, de Araujo, Leandro Ramos, Rodrigues, Victor T. S., and do Nascimento, Kelvin Bryan
- Abstract
Locating high impedance faults (HIF) in a distribution system increases the system’s reliability and improves the service’s quality for customers. However, this type of fault produces currents of low magnitude, making it difficult to locate using conventional techniques. Therefore, this paper proposes a method for the location of single-phase high impedance faults in distribution systems with photovoltaic cells in low voltage. The method is based on the use of the sequence component of the current circulating in the medium voltage feeders of the distribution system, which are obtained from synchronized phasorial meters positioned along the feeder. The method considers nonsymmetrical lines, unbalanced loads, capacitors banks, photovoltaic DGs, and load variation. The performance of the proposed method was evaluated and tested on several distribution systems using ATP or PSCAD® and the results show that the method can locate HIFs with high precision. Also, a comparison was made with recently published methods to show the efficiency of the proposed method. [ABSTRACT FROM AUTHOR]
- Published
- 2022
- Full Text
- View/download PDF
5. Common Mode Power Control of Three-Phase Inverter for Auxiliary Load Without Access to Neutral Point.
- Author
-
Tang, Junfei, Pehrman, Daniel, Mademlis, Georgios, and Liu, Yujing
- Subjects
- *
ELECTRICAL load , *MUTUAL inductance , *VECTOR spaces , *ELECTRIC inverters , *COMPRESSORS , *LOW voltage systems , *POWER electronics - Abstract
The purpose of this article is to investigate the potential of obtaining an auxiliary dc output from the common-mode switching harmonics of a three-phase inverter without access to the neutral point of the ac load. To achieve this, the control of common-mode (CM) switching harmonics with space vector modulation is proposed. With this control, CM switching harmonics can be regulated independently from the differential mode power flow to the main three-phase load. To physically implement the CM power flow, a harmonic extraction circuit is placed in parallel with the main three-phase load. The extraction circuit is formed by series-connected inductance and capacitance. Due to the LC series resonance and the mutual coupling of the inductance, only common-mode switching harmonics can pass through the extraction circuit. The extracted harmonics are then rectified and delivered to the auxiliary dc output. The control and topology are verified in both simulations and experiments. In the end, it is shown in experiments that there is no significant difference of the inverter efficiency after the auxiliary dc load is connected. This method can be used for instance to drive an ac machine while charging a low voltage battery or powering a compressor simultaneously. [ABSTRACT FROM AUTHOR]
- Published
- 2022
- Full Text
- View/download PDF
6. Modeling, Control, and Experimental Evaluation of Multifunctional Converter System.
- Author
-
Zhang, Xiaokang, Gauthier, Jean-Yves, Lin-Shi, Xuefang, Delpoux, Romain, and Tregouet, Jean-Francois
- Subjects
- *
ALTERNATING current electric motors , *PERMANENT magnet motors , *PERMANENT magnets , *DEGREES of freedom , *VECTOR spaces - Abstract
The multifunctional converter system (MFCS) is a special topology of three-phase ac motor drives, which inherently integrates a dc-voltage regulation function. First, in order to explain the mechanism of the MFCS, an average model is derived in this article. An equivalent circuit is developed, which explicitly reveals that the MFCS is equivalent to a cascaded dc/dc converter-dc motor drive system. Second, the inverter's mean duty cycle is identified as an independent control degree of freedom for the dc-bus voltage. Then, the influence of pulsewidth modulation (PWM) on the dc-bus voltage is studied. It concludes that space vector PWM is invalid for the MFCS. To address this problem, the zero-sequence voltage injection PWM (ZSVIPWM) is proposed and actually sinusoidal PWM is a special case of the ZSVIPWM. Third, an overall control strategy is proposed for the MFCS, which includes not only the vector control for the motor but also a closed-loop control for the dc-bus voltage. Finally, comparative experiments with the standard topology are carried out on a permanent magnet synchronous machine prototype to verify these theoretical analyses and the control strategy. [ABSTRACT FROM AUTHOR]
- Published
- 2021
- Full Text
- View/download PDF
7. Estimating zero-sequence impedance of three-terminal transmission line and Thevenin impedance using relay measurement data
- Author
-
Swagata Das, Sundaravaradan Navalpakkam Ananthan, and Surya Santoso
- Subjects
Zero-sequence ,Three-terminal line ,Thevenin Impedance ,Distribution or transmission of electric power ,TK3001-3521 ,Production of electric energy or power. Powerplants. Central stations ,TK1001-1841 - Abstract
Abstract Current and voltage waveforms recorded by intelligent electronic devices (IEDs) are more useful than just performing post-fault analysis. The objective of this paper is to present techniques to estimate the zero-sequence line impedance of all sections of a three-terminal line and the Thevenin equivalent impedance of the transmission network upstream from the monitoring location using protective relay data collected during short-circuit ground fault events. Protective relaying data from all three terminals may not be always available. Furthermore, the data from each terminal may be unsynchronized and collected at different sampling rates with dissimilar fault time instants. Hence, this paper presents approaches which use unsynchronized measurement data from all the terminals as well as data from only two terminals to estimate the zero-sequence line impedance of all the sections of a three-terminal line. An algorithm to calculate positive-, negative- and zero-sequence Thevenin impedance of the upstream transmission network has also been presented in this paper. The efficacy of the proposed algorithms are demonstrated using a test case. The magnitude error percentage in determining the zero-sequence impedance was less than 1% in the test case presented.
- Published
- 2018
- Full Text
- View/download PDF
8. A New Method for Dimensioning and Designing the Zero-Sequence Electromagnetic Filter Considering System Displacement Power Factor.
- Author
-
Fonseca Buzo, Ricardo, de Oliveira, Luis Carlos Origa, and Leao, Fabio Bertequini
- Subjects
- *
FILTERS & filtration , *MAGNETIC coupling , *TEST systems , *HARMONIC suppression filters , *ELECTRIC power filters - Abstract
This paper proposes an innovative method for dimensioning and designing the zero-sequence electromagnetic filter applied to three-phase four-wire distribution power systems. As premises, the optimum ratio between zero-sequence and positive-sequence impedances of the filter must be established in order to potentiate the filtering percentage of zero-sequence currents and ensure the quality of the supply system displacement power factor. The calculations are based on the sequential harmonic transmittances of the equivalent circuit reduced to the coupling point of the electromagnetic filter. To validate the proposed method, the results obtained with the application of the electromagnetic filter designed in a test system using the MATLAB software are compared to the results of the system modeled in the PSIM software. [ABSTRACT FROM AUTHOR]
- Published
- 2020
- Full Text
- View/download PDF
9. Zero-sequence voltage compensation of a distribution network through a four-wire modular multilevel static synchronous compensator.
- Author
-
Duarte, Samuel N., Ghetti, Frederico T., de Almeida, Pedro M., and Barbosa, Pedro G.
- Subjects
- *
SYNCHRONOUS capacitors , *SYNCHRONOUS electric motors , *VOLTAGE regulators , *ELECTRIC potential , *WAGES - Abstract
Highlights • Zero-sequence network voltage compensation strategy. • Modular mulitlevel static synchronous compensator. • Control algorithm for four-wire static synchronous compensator. Abstract This paper presents a zero-sequence voltage compensation strategy for a three-phase four-wire modular multilevel static synchronous compensator used to regulate the network voltages. The control strategy is based on a synchronous reference frame mathematical modelling used to control the positive and zero-sequence voltages and currents of a MMC static synchronous compensator. The static compensator is controlled to synthesize AC currents in such a way to restore the positive-sequence voltage to its rated value and to mitigate the zero-sequence voltage at the point of common coupling. Digital simulations are presented to validate the static synchronous compensator mathematical analysis and to demonstrate the performance of the proposed control strategy. [ABSTRACT FROM AUTHOR]
- Published
- 2019
- Full Text
- View/download PDF
10. Estimating Zero-Sequence Line Impedance and Fault Resistance Using Relay Data.
- Author
-
Das, Swagata, Ananthan, Sundaravaradan Navalpakkam, and Santoso, Surya
- Abstract
Data recorded by intelligent electronic devices such as protective relays contain a wealth of valuable information that can be used beyond post-mortem analysis of fault events. The objective of this paper is to propose algorithms to estimate zero-sequence line impedance and fault resistance using protective relay data collected during short-circuit fault events. Protective relaying data may be available from one or both ends of the line. For the latter, they may be collected at different sampling rates with dissimilar fault time instants. Furthermore, they may be unsynchronized. This paper presents approaches which uses measurement data from one and both ends of the line. The efficacy of the proposed algorithms presented in this paper are demonstrated using a test case as well as field data. The error percentage of the zero-sequence line impedance magnitude estimated using the data from both ends of a two-terminal line was under 3% for all the test cases. The error percentage in estimating the fault resistance was less than 1% in the test cases presented. [ABSTRACT FROM AUTHOR]
- Published
- 2019
- Full Text
- View/download PDF
11. Common Mode Power Control of Three-Phase Inverter for Auxiliary Load Without Access to Neutral Point
- Author
-
Junfei Tang, Daniel Pehrman, Georgios Mademlis, and Yujing Liu
- Subjects
Physics ,Other Electrical Engineering, Electronic Engineering, Information Engineering ,020208 electrical & electronic engineering ,Topology (electrical circuits) ,02 engineering and technology ,Control Engineering ,common mode (CM) ,Inductance ,Control theory ,Power electronics ,Harmonics ,Signal Processing ,0202 electrical engineering, electronic engineering, information engineering ,Harmonic ,Inverter ,Switching Harmonics ,Zero-Sequence ,Electrical and Electronic Engineering ,Power Electronics ,Low voltage ,Space vector modulation - Abstract
The purpose of this article is to investigate the potential of obtaining an auxiliary dc output from the common-mode switching harmonics of a three-phase inverter without access to the neutral point of the ac load. To achieve this, the control of common-mode (CM) switching harmonics with space vector modulation is proposed. With this control, CM switching harmonics can be regulated independently from the differential mode power flow to the main three-phase load. To physically implement the CM power flow, a harmonic extraction circuit is placed in parallel with the main three-phase load. The extraction circuit is formed by series-connected inductance and capacitance. Due to the LC series resonance and the mutual coupling of the inductance, only common-mode switching harmonics can pass through the extraction circuit. The extracted harmonics are then rectified and delivered to the auxiliary dc output. The control and topology are verified in both simulations and experiments. In the end, it is shown in experiments that there is no significant difference of the inverter efficiency after the auxiliary dc load is connected. This method can be used for instance to drive an ac machine while charging a low voltage battery or powering a compressor simultaneously.
- Published
- 2022
- Full Text
- View/download PDF
12. Input Voltage Sensorless Duty Compensation Control for a Three-Phase Boost PFC Converter.
- Author
-
Mallik, Ayan, Ding, Weisheng, Shi, Chuan, and Khaligh, Alireza
- Subjects
- *
CONVERTERS (Electronics) , *ELECTRIC power factor , *ELECTRICAL harmonics , *DIRECT currents , *PROTOTYPES - Abstract
This paper proposes an input voltage sensorless control algorithm for three-phase active boost rectifiers. Using this approach, the input ac-phase voltages can be accurately estimated from the fluctuations of other measured state variables and preceding switching state information from converter dynamics. Furthermore, the proposed control strategy reduces the input current harmonics of an ac–dc three-phase boost power factor correction (PFC) converter by injecting an additional common-mode duty ratio term to the feedback controllers’ outputs. This additional duty compensation term cancels the unwanted input harmonics, caused by the floating potential between ac source neutral and dc link negative, without requiring any access to the neutral point. A 6-kW (continuous power)/10-kW (peak power) three-phase boost PFC prototype using SiC-based semiconductor switching devices is designed and developed to validate the proposed control algorithm. The experimental results show that an input power factor of 0.999 with a conversion efficiency of 98.3%, total harmonic distortion as low as 4%, and a tightly regulated dc-link voltage with 1% ripple can be achieved. [ABSTRACT FROM PUBLISHER]
- Published
- 2017
- Full Text
- View/download PDF
13. A novel fault line selection method based on empirical mode decomposition and differential spectrum
- Author
-
ZHENG Chen, WANG Xiao-wei, LIU Ya-juan, and TIAN Shu
- Subjects
small current grounding system ,single-phase grounding fault ,fault line selection ,empirical mode decomposition ,high-frequency imf1 component ,differential spectrum ,fluctuation value ,zero-sequence ,Mining engineering. Metallurgy ,TN1-997 - Abstract
The paper proposed a novel single-phase grounding fault line selection method of small current grounding system based on EMD and differential spectrum. The method uses EMD method to decompose transient zero-sequence current and extract high-frequency IMF1 component of each line, obtained differential spectrum and fluctuation value of IMF1 component of each line according to definitions of differential spectrum and fluctuation value, and found out the fault line which has the maximum fluctuation value of IMF1 component by comparing fluctuation values of IMF1 component of each line. The experiment results showed that the method has higher accuracy of line selection and is suitable for fault line selection of small current grounding system under different grounding resistances and different fault initial phase angles.
- Published
- 2013
14. A Novel Zero-Sequence Model-Based Sensorless Method for Open-Winding PMSM With Common DC Bus.
- Author
-
Zhan, Hanlin, Zhu, Z. Q., Odavic, Milijana, and Li, Yanxin
- Subjects
- *
SENSORLESS control systems , *DIRECT currents , *ELECTRIC potential , *TRANSDUCERS , *ELECTRIC currents - Abstract
This paper proposes a zero-sequence model-based sensorless control strategy for open-winding permanent-magnet synchronous machine (OW-PMSM) with common dc bus. The third harmonic back electromotive force (EMF) in zero-sequence is utilized to estimate the rotor position information. The novelty is that the third harmonic back EMF is reconstructed based on the zero-sequence model together with zero-sequence current, instead of using voltage transducer and three phase resistance network which can be eliminated from the control system. Due to the essence of back EMF, the developed method is appropriate for the applications including wind power generation and motor drives operating above certain speed. Meanwhile, the phase shift-based space vector pulse width modulation method for OW-PMSM is also presented for easier implementation to form zero voltage disturbance in zero-sequence from the inverter side and hence the corresponding influence can be consequently minimized. The torque ripple, loss, and parameter sensitivity analysis are also carried out, as confirmed by predictions of two-dimensional finite element analysis. Due to the essence of decouple, the estimation can be more robust than the conventional fundamental model-based sensorless methods. Finally, the effectiveness of the proposed method is validated experimentally on a 3-kW OW-PMSM drive system with 2.5 kg·m2 total inertia. [ABSTRACT FROM AUTHOR]
- Published
- 2016
- Full Text
- View/download PDF
15. Suppression of Real Power Back Flow of Nonregenerative Cascaded H-Bridge Inverters Operating Under Faulty Conditions.
- Author
-
Sun, Le, Wu, Zhenxing, Xiao, Fei, Cai, Xinjian, and Wang, Shuxiu
- Subjects
- *
CASCADE converters , *ELECTRIC inverters , *ELECTRIC potential , *FAULT tolerance (Engineering) , *NIOBIUM , *ELECTRONIC modulation - Abstract
When the faulty cells of a nonregenerative cascaded H-bridge inverter are bypassed, it is necessary to inject a zero-sequence voltage into the inverter phase voltages so as to achieve the maximum balanced line-to-line voltage. However, the injected zero-sequence voltage may lead to a back flow of real power (BFRP) in at least one phase so that the dc voltage will rise to an intolerable level. To solve the problem, this paper proposes a new method of generating zero-sequence voltages. This method can not only maximize the available output voltage but also suppress the BFRP effectively. The zero-sequence voltage is always limited to an appropriate range to achieve the maximum output voltage through linear modulation. Closed-loop control is used to minimize the fundamental component of the zero-sequence voltage so that the power is less likely to flow back. Compared with the conventional methods, the proposed method allows the inverter to drive a load with a lower power factor not inducing BFRP or degrading the output voltage capability. As a result, the probability of overvoltage on the dc side is reduced. The experimental results show that the proposed method is effective and feasible. [ABSTRACT FROM AUTHOR]
- Published
- 2016
- Full Text
- View/download PDF
16. A three-phase power flow algorithm for ungrounded network based on constraints of zero-sequence components.
- Author
-
Zhang, Yi, Lin, Jinrong, and Li, Chuandong
- Subjects
- *
ELECTRICAL load , *LAPLACIAN matrices , *VOLTAGE references , *NEWTON-Raphson method , *MATHEMATICAL analysis - Abstract
• The paper constrains the zero-sequence currents of the ungrounded winding nodes to zero, and combines with the power equations and the Newton Raphon method to propose a three-phase power flow algorithm for ungrounded distribution networks. • The paper analyzes (a) the convergence problem of the method that constrains squares of zero-sequence voltages and currents to zero based on mathematical derivation and (b) the inapplicability problem of the method that constrains zero-sequence voltages to zero of the ungrounded winding nodes based on both a theoretical analysis and verification by examples. • The algorithm proposed in the paper is universally applicable, and has a low computation time, high efficiency and good convergence performance. It has the potential to be widely applicable to engineering practice. The existing research on three-phase power flow in ungrounded distribution networks primarily adopts the methods of presetting zero-sequence reference voltages and neutral point reference voltages. This makes it impossible to calculate the power flow in ungrounded network with non-zero neutral point voltages or zero-sequence voltages. Furthermore, a unified zero-sequence components constraint method of ungrounded distribution network does not exist. In this paper, a three-phase power flow algorithm is proposed to calculate three-phase power flow in an ungrounded distribution network. First, power flow equation variables, transformer admittance matrices and zero-sequence components are used to analyze the characteristic of three-phase power flow in an ungrounded distribution network. Second, a three-phase power flow algorithm for ungrounded distribution network is designed by constraining the zero-sequence currents of the ungrounded winding nodes to zero. Third, theoretical analyses and mathematical derivations are used to prove the applicability of the two methods, one of which constrains zero-sequence voltages of ungrounded winding nodes to zero and the other constrains squares of zero-sequence voltages and currents to zero. Last, a five-nodes network, modified IEEE123 network and practical network are used to demonstrate that the proposed method has a high accuracy and good applicability in calculating the three-phase power flow of ungrounded distribution networks. [ABSTRACT FROM AUTHOR]
- Published
- 2023
- Full Text
- View/download PDF
17. A Control Strategy for Suppressing Circulating Currents in Parallel-Connected PMSM Drives With Individual DC Links.
- Author
-
Wang, Fei, Wang, Yong, Gao, Qiang, Wang, Chengmin, and Liu, Yubing
- Subjects
- *
PERMANENT magnets , *SYNCHRONOUS electric motors , *CASCADE converters , *MOTOR drives (Electric motors) , *ELECTRIC current rectifiers , *ELECTRIC inductance , *ELECTRIC switchgear - Abstract
This paper proposes a novel circulating-current control strategy applied in back-to-back parallel three-phase converters with individual dc links for permanent magnet synchronous motor (PMSM) drives. First, the zero-sequence circulating current and the cross current paths in the whole parallel system are analyzed. Then, the models of an n-paralleled subsystem with individual dc links in both the three-phase stationary coordinates and the synchronous rotating coordinates are built up, which explores the fundamental mechanism of circulating current. Based on the analysis, a novel control strategy can suppress the circulating current at the motor side. The control system consists of two main loops in the d-axis, q-axis, and zero-axis, which are defined in this paper as sum control and difference control. The proposed control strategy effectively suppresses the circulating current in both steady-state and transient operations. The zero-sequence circulating current is greatly reduced by the difference control on the zero-axis. In addition, the bandwidth of the controllers is greatly improved, especially when the current-sharing inductance is much smaller than the stator inductance. Finally, with a PMSM load, the simulation and experiment results are presented to verify the theoretical analysis and proposed control strategy. [ABSTRACT FROM PUBLISHER]
- Published
- 2016
- Full Text
- View/download PDF
18. Comparative study of reference currents and DC bus voltage control for Three-Phase Four-Wire Four-Leg SAPF to compensate harmonics and reactive power with 3D SVM.
- Author
-
Chebabhi, A., Fellah, M.K., Kessal, A., and Benkhoris, M.F.
- Subjects
DIRECT currents ,VOLTAGE control ,ELECTRIC power filters ,ELECTRICAL harmonics ,SUPPORT vector machines ,SLIDING mode control - Abstract
In this paper the performances of three reference currents and DC bus voltage control techniques for Three-Phase Four-Wire Four-Leg SAPF are compared for balanced and unbalanced load conditions. The main goals are to minimize the harmonics, reduce the magnitude of neutral current, eliminate the zero-sequence current components caused by single-phase nonlinear loads and compensate the reactive power, and on the other hand improve performances such as robustness, stabilization, trajectory pursuit, and reduce time response. The three techniques are analyzed mathematically and simulation results are compared. The techniques considered for comparative study are the PI Control, Sliding Mode Control and the Backstepping Control. Synchronous reference frame theory (SRF) in the dqo-axes is used to generate the reference currents, of the inverter. [ABSTRACT FROM AUTHOR]
- Published
- 2015
- Full Text
- View/download PDF
19. Current control assisted and non-ideal Proportional-Resonant voltage controller for four-leg three-phase inverters with time-variant loads.
- Author
-
Nazifi, Hamed and Radan, Ahmad
- Abstract
In this paper a novel control strategy for four-leg three-phase voltage source inverters (VSI) supplying time variant loads is proposed. Designed control scheme is composed of three parts: A feed-forward current compensator; Inverter main Proportional-Resonant (PR) voltage controller; and inverter output current controller. The PR controller is employed for regulating the output voltage of inverter to produce a symmetrical balanced three-phase voltage under different loading conditions such as balanced, unbalanced, linear, non-linear variant loads. The inverter current control loop designed with state feed-back methods improves the system response. The performance of proposed control strategy is studied under different loading conditions. Simulation results depict marvelous performance of the proposed controller in dynamic and steady states. [ABSTRACT FROM PUBLISHER]
- Published
- 2013
- Full Text
- View/download PDF
20. Modeling, Control and Experimental Evaluation of Multi-functional Converter System
- Author
-
Romain Delpoux, Xuefang Lin-Shi, Jean-Francois Tregouet, Xiaokang Zhang, Jean-Yves Gauthier, Ampère, Département Méthodes pour l'Ingénierie des Systèmes (MIS), Ampère (AMPERE), École Centrale de Lyon (ECL), Université de Lyon-Université de Lyon-Université Claude Bernard Lyon 1 (UCBL), Université de Lyon-Institut National des Sciences Appliquées de Lyon (INSA Lyon), Université de Lyon-Institut National des Sciences Appliquées (INSA)-Institut National des Sciences Appliquées (INSA)-Centre National de la Recherche Scientifique (CNRS)-Institut National de Recherche pour l’Agriculture, l’Alimentation et l’Environnement (INRAE)-École Centrale de Lyon (ECL), and Université de Lyon-Institut National des Sciences Appliquées (INSA)-Institut National des Sciences Appliquées (INSA)-Centre National de la Recherche Scientifique (CNRS)-Institut National de Recherche pour l’Agriculture, l’Alimentation et l’Environnement (INRAE)
- Subjects
Vector control ,Computer science ,020208 electrical & electronic engineering ,Topology (electrical circuits) ,02 engineering and technology ,AC motor ,[SPI.AUTO]Engineering Sciences [physics]/Automatic ,zero-sequence ,Motor drive ,[SPI]Engineering Sciences [physics] ,Control and Systems Engineering ,Control theory ,Duty cycle ,DC/DC converter ,0202 electrical engineering, electronic engineering, information engineering ,Equivalent circuit ,Permanent magnet synchronous machine drives ,neutral point ,Electrical and Electronic Engineering ,Synchronous motor ,Pulse-width modulation - Abstract
International audience; The multi-functional converter system (MFCS) is a special topology of three-phase AC motor drives, which inherently integrates a DC-voltage regulation function. Firstly, in order to explain the mechanism of the MFCS, an average model is derived. An equivalent circuit is developed, which explicitly reveals that the MFCS is equivalent to a cascaded DC/DC converter-DC motor drive system. Secondly, the inverter's mean duty-cycle is identified as an independent control degree of freedom for the DC-bus voltage. Then, the influence of pulse width modulation (PWM) on the DC-bus voltage is studied. It concludes that space vector PWM is invalid for the MFCS. To address this problem, the zero-sequence voltage injection PWM (ZSVIPWM) is proposed and actually sinusoidal PWM is a special case of the ZSVIPWM. Thirdly, an overall control strategy is proposed for the MFCS, which includes not only the vector control for the motor but also a closed-loop control for the DC-bus voltage. Finally, comparative experiments with the standard topology are carried out on a permanent magnet synchronous machine prototype to verify these theoretical analyses and the control strategy.
- Published
- 2020
- Full Text
- View/download PDF
21. A New Method for Dimensioning and Designing the Zero-Sequence Electromagnetic Filter Considering System Displacement Power Factor
- Author
-
Luis Carlos Origa de Oliveira, Fabio Bertequini Leao, Ricardo Fonseca Buzo, and Universidade Estadual Paulista (Unesp)
- Subjects
Electromagnetics ,Mitigation ,Computer science ,020209 energy ,designing ,Resistance ,electromagnetic filter ,Energy Engineering and Power Technology ,02 engineering and technology ,Power factor ,Power harmonic filters ,Electric power system ,Control theory ,0202 electrical engineering, electronic engineering, information engineering ,Electrical and Electronic Engineering ,MATLAB ,Inductance ,Dimensioning ,Magnetic flux ,computer.programming_language ,Coils ,Filter (signal processing) ,zero-sequence ,dimensioning ,Harmonic ,Equivalent circuit ,Legged locomotion ,computer - Abstract
Made available in DSpace on 2020-12-10T20:01:16Z (GMT). No. of bitstreams: 0 Previous issue date: 2020-06-01 Coordenação de Aperfeiçoamento de Pessoal de Nível Superior (CAPES) Conselho Nacional de Desenvolvimento Científico e Tecnológico (CNPq) Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP) This paper proposes an innovative method for dimensioning and designing the zero-sequence electromagnetic filter applied to three-phase four-wire distribution power systems. As premises, the optimum ratio between zero-sequence and positive-sequence impedances of the filter must be established in order to potentiate the filtering percentage of zero-sequence currents and ensure the quality of the supply system displacement power factor. The calculations are based on the sequential harmonic transmittances of the equivalent circuit reduced to the coupling point of the electromagnetic filter. To validate the proposed method, the results obtained with the application of the electromagnetic filter designed in a test system using the MATLAB software are compared to the results of the system modeled in the PSIM software. Sao Paulo State Univ, Dept Elect Engn, BR-15385000 Ilha Solteira, Brazil Sao Paulo State Univ, Dept Elect Engn, BR-15385000 Ilha Solteira, Brazil CAPES: 001 FAPESP: 2015/21972-6
- Published
- 2020
22. A Novel Method of Fault Line Selection in Low Current Grounding System using Multi-criteria Information Integrated.
- Author
-
Shen, Qihao
- Subjects
- *
MEMBERSHIP functions (Fuzzy logic) , *SYSTEM safety , *SIGNAL processing - Abstract
• The basis for the selection of multi-criteria fault line selection is given. • The proposed method avoids the complex signal processing and analysis process. • Avoid misjudgments caused by unbalanced load current interference. • Simplifies the fault identification process by means of comprehensive criteria. Single-phase grounding faults often occur in low-current grounding systems, and the selection of fault lines is an important factor affecting the reliability and safety of the distribution system. Aiming at the problem that the existing line selection criteria may cause misjudgment, this paper makes full use of the changes in the amount of fault information during the occurrence of a fault and proposes a multi-criteria line selection basis that integrates fault information. Since different neutral grounding methods will affect the change of the fault state quantity, the characteristic changes of the fault state quantity under different neutral grounding methods are fully discussed, and different fault quantities are selected as the basis for line selection. In addition, a membership function and a weight coefficient function are respectively set to indicate the possibility and credibility of a single criterion line selection result. The weighted summation of the membership functions corresponding to multiple criteria completes the information integration of multiple criteria, and the formed composite criterion reduces the proportion of misjudgments. The simulation experiment data proves that the proposed method can correctly, effectively, and reliably select faulty lines, greatly reduce the possibility of misjudgment and improve the efficiency and universality of line selection. [ABSTRACT FROM AUTHOR]
- Published
- 2022
- Full Text
- View/download PDF
23. Analysis and Control of a Single-Phase-Inverter-Zigzag-Transformer Hybrid Neutral-Current Suppressor in Three-Phase Four-Wire Systems.
- Author
-
Sewan Choi and Minsoo Jang
- Subjects
- *
ELECTRIC transformers , *ELECTRICAL harmonics , *ELECTRIC waves , *CAPACITORS , *ELECTRIC current rectifiers , *ELECTRIC machinery , *PROTOTYPES - Abstract
This paper presents analysis and control of a hybrid filter that can suppress neutral harmonic currents in three-phase four-wire systems not only with harmonic voltage-source loads but also with harmonic current-source loads. The filter voltampere rating is significantly reduced compared to the conventional neutral-current-suppressing methods. The rectifier part of the neutral harmonic suppressor has been removed by controlling the dc capacitor voltage. The experimental results on a 50-kVA prototype validate the proposed control approach. [ABSTRACT FROM AUTHOR]
- Published
- 2007
- Full Text
- View/download PDF
24. Variable speed wind turbine generator with zero-sequence filter
- Author
-
Muljadi, Eduard [Golden, CO]
- Published
- 1998
25. A circulating current suppression method for parallel connected voltage-source-inverters (VSI) with common DC and AC buses
- Author
-
Xiaoqiang Guo, Juan C. Vasquez, Baoze Wei, and Josep M. Guerrero
- Subjects
Parallel connected ,Engineering ,business.industry ,Cross circulating current ,020208 electrical & electronic engineering ,05 social sciences ,02 engineering and technology ,Common DC and AC buses ,Zero-sequence ,Electric power system ,Control theory ,Uninterruptible power system ,0202 electrical engineering, electronic engineering, information engineering ,Inverter ,0501 psychology and cognitive sciences ,Voltage droop ,Output impedance ,Voltage source ,business ,Electrical impedance ,Voltage source inverter ,050107 human factors ,Voltage reference ,Voltage - Abstract
This paper describes a theoretical with experiment study on a control strategy for the parallel operation of threephase voltage source inverters (VSI), to be applied touninterruptible power systems (UPS). A circulating current suppression strategy for parallel VSIs is proposed in this paper based on circulating current control loops used to modify the reference currents by compensating the error currents among parallel inverters. Both of the cross and zero-sequence circulating currents are considered. The proposed method is coordinated together with droop and virtual impedance control. In this paper, droop control is used to generate the reference voltage of each inverter, and the virtual impedance is used to fix the output impedance of the inverters. In addition, a secondary control is used in order to recover the voltage deviation caused by the virtual impedance. And the auxiliary current control loop is added to acquire a better average current sharing performance among parallel VSIs, which can effectively suppress both of thecross and zero-sequence circulating currents. Experimental results are presented in order to verify the effectiveness of the proposed control strategy.
- Published
- 2016
- Full Text
- View/download PDF
26. A Circulating-Current Suppression Method for Parallel-Connected Voltage-Source Inverters With Common DC and AC Buses
- Author
-
Josep M. Guerrero, Xiaoqiang Guo, Juan C. Vasquez, and Baoze Wei
- Subjects
Engineering ,020209 energy ,02 engineering and technology ,Industrial and Manufacturing Engineering ,voltage-source inverter ,cross circulating current ,Control theory ,0202 electrical engineering, electronic engineering, information engineering ,Electronic engineering ,Voltage droop ,Voltage source ,Electrical and Electronic Engineering ,Common dc and ac buses ,Electrical impedance ,Voltage source inverter ,Cross circulating-current ,business.industry ,020208 electrical & electronic engineering ,Zero sequence circulating current ,parallel connected ,Zero-sequence ,Control and Systems Engineering ,Control system ,Microgrid ,business ,Uninterruptible power supply ,Voltage drop ,Voltage - Abstract
This paper presents a theoretical study with experimental validation of a circulating-current suppression method for parallel operation of three-phase voltage source inverters (VSI), which may be suitable for modular parallel uninterruptible power supply systems or hybrid AC/DC microgrid applications. The basic concept of the proposed circulating-current suppression method is to modify the original current references by using the current difference among the parallel inverters. In the proposed approach, both of cross circulating-current and zero-sequence circulating-current are considered, and added into the conventional droop plus virtual impedance control. In the control architecture, the reference voltages of the inverters are generated by the primary control loop which consists of a droop control and a virtual impedance. The secondary control is used to compensate the voltage drop on the virtual impedance. Further, a circulating-current control loop is added to improve the average current-sharing performance among parallel VSIs. Experimental results are presented to show the effectiveness of the proposed control method to suppress both of the cross and zero-sequence circulating-currents.
- Published
- 2016
- Full Text
- View/download PDF
27. Estimating zero-sequence impedance of three-terminal transmission line and Thevenin impedance using relay measurement data.
- Author
-
Das, Swagata, Navalpakkam Ananthan, Sundaravaradan, and Santoso, Surya
- Subjects
ELECTRONIC equipment ,FAULT tolerance (Engineering) ,ELECTRIC impedance ,ELECTRIC lines ,OPEN-circuit voltage - Abstract
Current and voltage waveforms recorded by intelligent electronic devices (IEDs) are more useful than just performing post-fault analysis. The objective of this paper is to present techniques to estimate the zero-sequence line impedance of all sections of a three-terminal line and the Thevenin equivalent impedance of the transmission network upstream from the monitoring location using protective relay data collected during short-circuit ground fault events. Protective relaying data from all three terminals may not be always available. Furthermore, the data from each terminal may be unsynchronized and collected at different sampling rates with dissimilar fault time instants. Hence, this paper presents approaches which use unsynchronized measurement data from all the terminals as well as data from only two terminals to estimate the zero-sequence line impedance of all the sections of a three-terminal line. An algorithm to calculate positive-, negative- and zero-sequence Thevenin impedance of the upstream transmission network has also been presented in this paper. The efficacy of the proposed algorithms are demonstrated using a test case. The magnitude error percentage in determining the zero-sequence impedance was less than 1% in the test case presented. [ABSTRACT FROM AUTHOR]
- Published
- 2018
- Full Text
- View/download PDF
28. Procédé de commande d'un moteur électrique à 3 phases alimentée indépendamment
- Author
-
BRUYERE, Antoine, KESTELYN, Xavier, MEINGUET, Fabien, SANDULESCU, Paul, and SEMAIL, Eric
- Subjects
machine polyphasée, mode défluxé, homopolaire ,Energie électrique [Sciences de l'ingénieur] ,flux weakening ,zero-sequence ,open-windings ,Traitement du signal et de l'image [Sciences de l'ingénieur] - Abstract
Le système d’entraînement rotatif comporte : - une source de tension continue (102) ; - un moteur électrique (104) présentant un axe de rotation (A), et comportant des phases indépendantes (a, b, c) présentant des directions autour de 5 l’axe de rotation (A) ; - un onduleur (106) destiné à connecter chaque phase (a, b, c) à la source de tension continue (102) ; et - un dispositif de commande (110) destiné à fournir une commande à l’onduleur (106). Le dispositif de commande (110) comporte : - des moyens (118) de sélection de 10 formule, destinés à sélectionner une formule parmi des formules prédéterminées, chaque formule prédéterminée étant destinée à calculer soit une consigne de tension homopolaire, soit une consigne de courant homopolaire ; - des moyens (124) de détermination de consigne, destinés à appliquer la formule sélectionnée pour déterminer, suivant la formule sélectionnée, soit une consigne de tension homopolaire, 15 soit une consigne de courant homopolaire, et - des moyens (126) de détermination de commande, destinés à déterminer la commande de l’onduleur (106) à partir de la consigne déterminée. Projet SOFRACI/FUI
- Published
- 2013
29. Modeling and Control of Parallel Three-Phase PWM Converters
- Author
-
Ye, Zhihong, Electrical and Computer Engineering, Boroyevich, Dushan, Lai, Jih-Sheng, Chen, Dan Y., Lee, Fred C., and Nayfeh, Ali H.
- Subjects
zero-sequence ,current-bidirectional ,PWM converters ,parallel ,four-leg converter ,three-phase ,load sharing ,current-unidirectional ,common-mode noise ,multi-phase converter ,circulating current - Abstract
This dissertation studies modeling and control issues of parallel three-phase pulse-width modulated (PWM) converters. The converters include three-phase boost rectifiers, voltage source inverters, buck rectifiers and current source inverters. The averaging of the parallel converters is performed based on a generic functional switching unit, which is called a phase leg in boost rectifiers and voltage source inverters, and a rail arm in buck rectifiers and current source inverters. Based on phase-leg and rail-arm averaging, the developed models are not only equivalent to the conventional three-phase converter models that are based on phase-to-phase averaging, but they also preserve common-mode information, which is critical in the analysis of the parallel converters. The models reveal such parallel dynamics as reactive power circulation and small-signal interaction. A unique feature of the parallel three-phase converters is a zero-sequence circulating current. This work proposes a novel zero-sequence control concept that uses variable zero-vectors in the space-vector modulation (SVM) of the converters. The control can be implemented within an individual converter and is independent from the other control loops for the converter. Therefore, it greatly facilitates the design and expansion of a parallel system. Proper operation of the parallel converters requires an explicit load-sharing mechanism. In order to have a modular design, a droop method is recommended. Traditionally, however, a droop method has to compromise between voltage regulation and load sharing. After parametric analysis, a novel droop method using a gain-scheduling technique is proposed. The numeric analysis shows that the proposed droop method can achieve both good voltage regulation and good load sharing. An interleaving technique is often used in parallel converter systems in order to reduce current ripples. Because of its symmetrical circuit structure, the parallel three-phase converter system can reduce both differential-mode and common-mode noise with a center-aligned symmetrical SVM. Based on the concept that a symmetrical circuit can reduce common-mode dv/dt noise, a conventional three-phase, four-leg inverter is modified so that its fourth leg is symmetrical to the other three legs. The common-mode dv/dt noise can be practically eliminated with a new modulation strategy. Meanwhile, with a modified control design, the new four-leg inverter still can handle low-frequency common-mode components that occur due to unbalanced and nonlinear load. Ph. D.
- Published
- 2000
30. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Byrtus, Jiří, Topolánek, David, Paar, Martin, and Byrtus, Jiří
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
31. Simulace účinků zkratových proudů v rozvodnách VVN
- Author
-
Toman, Petr, Buriánek, Jiří, Tománek, Miloslav, Toman, Petr, Buriánek, Jiří, and Tománek, Miloslav
- Abstract
Tato práce se zabývá teoretickým výpočtem zkratových proudů v elektrizační soustavě v souladu normou ČSN 60909-0 a především výpočtem dynamických a tepelných účinků zkratových proudů v rozvodnách VVN podle normy ČSN 60865-1. Dále se práce zabývá tvorbou programů pro simulaci mechanických účinků zkratových proudů s ohledem na dimenzování konstrukčních prvků rozvodny a praktickou simulací vybraných částí skutečné rozvodny typu "H" ve Slavkově u Brna., This thesis is engaged in a theoretical calculation of short-circuit currents in electric power system in compliance with the norm ČSN 60909-0 and first of all with calculation of dynamical and thermal effects of short-circuit currents in HV switching stations in accordance with the norm ČSN 60865-1. Next the thesis is engaged in a production of programs for simulation of mechanical effects of short-circuit currents with respect to a dimensioning of constructional elements of switching station and afterwards in a practical simulation of selected parts of the real switching station type „H“ in Slavkov u Brna.
32. Simulace účinků zkratových proudů v rozvodnách VVN
- Author
-
Toman, Petr, Buriánek, Jiří, Tománek, Miloslav, Toman, Petr, Buriánek, Jiří, and Tománek, Miloslav
- Abstract
Tato práce se zabývá teoretickým výpočtem zkratových proudů v elektrizační soustavě v souladu normou ČSN 60909-0 a především výpočtem dynamických a tepelných účinků zkratových proudů v rozvodnách VVN podle normy ČSN 60865-1. Dále se práce zabývá tvorbou programů pro simulaci mechanických účinků zkratových proudů s ohledem na dimenzování konstrukčních prvků rozvodny a praktickou simulací vybraných částí skutečné rozvodny typu "H" ve Slavkově u Brna., This thesis is engaged in a theoretical calculation of short-circuit currents in electric power system in compliance with the norm ČSN 60909-0 and first of all with calculation of dynamical and thermal effects of short-circuit currents in HV switching stations in accordance with the norm ČSN 60865-1. Next the thesis is engaged in a production of programs for simulation of mechanical effects of short-circuit currents with respect to a dimensioning of constructional elements of switching station and afterwards in a practical simulation of selected parts of the real switching station type „H“ in Slavkov u Brna.
33. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Byrtus, Jiří, Topolánek, David, Paar, Martin, and Byrtus, Jiří
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
34. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Topolánek, David, and Paar, Martin
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
35. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Topolánek, David, and Paar, Martin
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
36. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Topolánek, David, and Paar, Martin
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
37. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Topolánek, David, and Paar, Martin
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
38. Simulace účinků zkratových proudů v rozvodnách VVN
- Author
-
Toman, Petr, Buriánek, Jiří, Toman, Petr, and Buriánek, Jiří
- Abstract
Tato práce se zabývá teoretickým výpočtem zkratových proudů v elektrizační soustavě v souladu normou ČSN 60909-0 a především výpočtem dynamických a tepelných účinků zkratových proudů v rozvodnách VVN podle normy ČSN 60865-1. Dále se práce zabývá tvorbou programů pro simulaci mechanických účinků zkratových proudů s ohledem na dimenzování konstrukčních prvků rozvodny a praktickou simulací vybraných částí skutečné rozvodny typu "H" ve Slavkově u Brna., This thesis is engaged in a theoretical calculation of short-circuit currents in electric power system in compliance with the norm ČSN 60909-0 and first of all with calculation of dynamical and thermal effects of short-circuit currents in HV switching stations in accordance with the norm ČSN 60865-1. Next the thesis is engaged in a production of programs for simulation of mechanical effects of short-circuit currents with respect to a dimensioning of constructional elements of switching station and afterwards in a practical simulation of selected parts of the real switching station type „H“ in Slavkov u Brna.
39. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Byrtus, Jiří, Topolánek, David, Paar, Martin, and Byrtus, Jiří
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
40. Výpočet zkratových poměrů v lokální distribuční soustavě
- Author
-
Topolánek, David, Paar, Martin, Byrtus, Jiří, Topolánek, David, Paar, Martin, and Byrtus, Jiří
- Abstract
Tato práce se zabývá přechodovými jevy v elektrizační soustavě, především zkraty. V první části jsou popsány druhy zkratů, příčiny jejich vzniku i následky jejich působení. Dále zobrazuje časové průběhy zkratových proudů a jejich složek. Je zde uvedena metoda výpočtu zkratových proudů pomocí složkových soustav a určeny základní vztahy pro výpočet zkratových impedancí. Vztahy a metody výpočtu vycházejí z platné normy ČSN EN 60909 – 0. V druhé části je uveden výpočet zkratových proudů konkrétní sítě průmyslového objektu. Ten má za cíl ověřit dimenzování rozvoden na zkratové proudy po připojení synchronního generátoru zadaného výkonu do soustavy., This thesis deals with transient phenomena in the electricity grid - especially with short-circuits. First part describes short-circuit types, reasons for their commencement and also consequences of their functioning. The thesis further shows waveforms of short-circuit currents and its components. A method of calculating short-circuits currents, using the constituent systems and the basic equations for calculating short-circuit impedances are also mentioned here. Relations and methods are based on valid standards of IEC 60909 – 0. The second part indicates the calculation of two-phase and three-phase short-circuit currents for specific network of industrial building. This calculation aims to verify the dimensioning of substations for short-circuit currents after connecting a synchronous generator with given power to the main substation.
41. Simulace účinků zkratových proudů v rozvodnách VVN
- Author
-
Toman, Petr, Buriánek, Jiří, Tománek, Miloslav, Toman, Petr, Buriánek, Jiří, and Tománek, Miloslav
- Abstract
Tato práce se zabývá teoretickým výpočtem zkratových proudů v elektrizační soustavě v souladu normou ČSN 60909-0 a především výpočtem dynamických a tepelných účinků zkratových proudů v rozvodnách VVN podle normy ČSN 60865-1. Dále se práce zabývá tvorbou programů pro simulaci mechanických účinků zkratových proudů s ohledem na dimenzování konstrukčních prvků rozvodny a praktickou simulací vybraných částí skutečné rozvodny typu "H" ve Slavkově u Brna., This thesis is engaged in a theoretical calculation of short-circuit currents in electric power system in compliance with the norm ČSN 60909-0 and first of all with calculation of dynamical and thermal effects of short-circuit currents in HV switching stations in accordance with the norm ČSN 60865-1. Next the thesis is engaged in a production of programs for simulation of mechanical effects of short-circuit currents with respect to a dimensioning of constructional elements of switching station and afterwards in a practical simulation of selected parts of the real switching station type „H“ in Slavkov u Brna.
42. Improved modeling of three-phase transformer analysis based on nonlinear BH curve and taking into account zero-sequence flux
- Author
-
Kawkabani, B. and Simond, J.-J.
- Subjects
zero-sequence ,modeling of three-phase transformer ,Transformer ,Flux ,Modeling ,Nonlinear ,Taking ,Account ,B-H Curve ,Three-Phase - Abstract
The present paper deals with a new approach for the study of the steady - state and transient behaviour of three- phase transformers. This approach based on magnetic equivalent circuit diagrams, takes into account the nonlinear B-H curve as well as zero-sequence flux. The nonlinear B-H curve is represented by a Fourier series, based on a set of measurement data. For the numerical simulations, two methods have been developed, by considering the total magnetic flux respectively the currents as state variables. Numerical results compared with test results and with FEM computations confirm tvalidity of the proposed approach.
Catalog
Discovery Service for Jio Institute Digital Library
For full access to our library's resources, please sign in.