Relevant Parameters in a Statistical Analysis—Application to Transmission-Line Energization.
- Source :
-
IEEE Transactions on Power Delivery . Dec2014, Vol. 29 Issue 6, p2605-2613. 9p. - Publication Year :
- 2014
-
Abstract
- This paper summarizes the important factors that affect statistical switching transients studies during transmission-line energization. These factors include the number of repetitions to ensure the statistical characteristic of the study, the variation range of the mean closing time of the circuit-breaker contacts, the model used for the representation of the transmission line, and the influence of transposition. In addition, a statistical analysis of mitigation methods to reduce overvoltages during transmission-line energization maneuver is presented, specifically the use of surge arresters, of controlled switching, and of a preinsertion resistor. The shunt compensation degree is considered as an independent parameter. Digital simulations were performed with PSCAD. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 08858977
- Volume :
- 29
- Issue :
- 6
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Delivery
- Publication Type :
- Academic Journal
- Accession number :
- 100027997
- Full Text :
- https://doi.org/10.1109/TPWRD.2014.2317875