Back to Search Start Over

Design and Application of a Second-Order High-Pass Damped Filter for 8000-hp ID Fan Drives—A Case Study.

Authors :
Das, J. C.
Source :
IEEE Transactions on Industry Applications. Mar2015, Vol. 51 Issue 2, p1417-1426. 10p.
Publication Year :
2015

Abstract

The design and application of second-order high-pass filters are described for 2-8000-hp ID fan drives, which reduces the voltage harmonic distortion at point of common coupling (PCC) from a high value of 42.41% to 1.32% and also brings the current distortion at PCC within IEEE 519 limits. Failure of the electronic components of the 8000-hp ID fan drives and shutdown of electronic loads downstream of the main 13.8-kV buses were observed, which led to investigation of harmonic problems and their mitigation. The second-order high-pass filters are applied for the first time in industry for such a harmonic distortion problem. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00939994
Volume :
51
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
101734156
Full Text :
https://doi.org/10.1109/TIA.2014.2356655