Back to Search Start Over

Experimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacement.

Authors :
Mota-Babiloni, Adrián
Navarro-Esbrí, Joaquín
Barragán-Cervera, Ángel
Molés, Francisco
Peris, Bernardo
Source :
International Journal of Refrigeration. Mar2015, Vol. 51, p52-58. 7p.
Publication Year :
2015

Abstract

This work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
01407007
Volume :
51
Database :
Academic Search Index
Journal :
International Journal of Refrigeration
Publication Type :
Academic Journal
Accession number :
102036671
Full Text :
https://doi.org/10.1016/j.ijrefrig.2014.12.010