Experimental study on the influence of the disconnecting switch operation on CVTs in UHV series compensation stations.

Authors :
Zhu, Lingyu
Ji, Shengchang
Li, Jinyu
Liu, Yuan
Source :
IEEE Transactions on Dielectrics & Electrical Insulation. Apr2015, Vol. 22 Issue 2, p925-933. 9p.
Publication Year :
2015

Abstract

In series compensation stations of the UHV AC demonstration project in China, capacitive voltage transformers (CVTs) failed several times during the operation of disconnecting switches (DSs). The reasons for this failure are analyzed in this paper. The stray inductor, the stray capacitor between the platform and ground and the capacitor of the CVT forms a resonant circuit in series compensation stations, causing repeated oscillating overvoltage and impulse current acting on the CVTs during DS operation. A full-scale experiment indicates that the oscillating frequency is approximately 200 Hz and the repeating frequency is approximately 0.5 MHz. The simulation experiment in the laboratory indicates that the partial welding mode and the partial high electric field are the main causes of damage to the CVT element insulation. A mechanism of the insulation damage is proposed, and some suggestions are given based on our results. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10709878
Volume :
22
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Dielectrics & Electrical Insulation
Publication Type :
Academic Journal
Accession number :
102086733
Full Text :
https://doi.org/10.1109/TDEI.2015.7076793