Back to Search Start Over

Modeling and Insulation Performance Analysis of Composite Transmission Line Tower Under Lightning Overvoltage.

Authors :
Huangfu, Youpeng
Wang, Shuhong
Wang, Guolin
Xu, Weijie
Zhang, Haijun
Source :
IEEE Transactions on Magnetics. Mar2015, Vol. 51 Issue 3, p1-4. 4p.
Publication Year :
2015

Abstract

In this paper, a new non-uniform multiconductor transmission line model combining with lumped circuit elements for a composite transmission line (TL) tower under lightning strokes is established. The metal ground-wire cross arms, the metal tower main body and its bracings are modeled as equivalent horizontal and vertical TLs, respectively. The two grounding ladders are regarded as two parallel–vertical TLs considering their mutual coupling. These distributed TL parameters are calculated by analytic equations. The composite arms are equivalent as lumped capacitances determined by employing 3-D finite-element method. The lightning overvoltage analysis for a 330-kV composite tower is performed by applying the hybrid model. The incident and reflected voltages are calculated. The insulation performance evaluation for the composite tower is discussed in detail. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00189464
Volume :
51
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Magnetics
Publication Type :
Academic Journal
Accession number :
102288314
Full Text :
https://doi.org/10.1109/TMAG.2014.2356859