Back to Search
Start Over
Estimation of Giardia Ct Values at High pH for the Surface Water Treatment Rule.
- Source :
-
Journal of Environmental Science & Health. Part A. Toxic/Hazardous Substances & Environmental Engineering . Sep2003, Vol. 38 Issue 9, p1959-1970. 12p. - Publication Year :
- 2003
-
Abstract
- The U.S. Environmental Protection Agency currently recommends Ct (disinfectant concentration multiplied by the exposure time) values to achieve required levels of inactivation of Giardia lamblia cysts by different disinfectants including free chlorine. Current guidance covers inactivation levels in the pH range between 6 and 9. Subsequent to the publication of these criteria, studies on the inactivation kinetics of Giardia cysts by chlorine have been performed at pH levels greater than 9. It has been shown that the chlorine inactivation process for Giardia cysts is pH dependent. The objective of this paper is to extend the current Ct values for higher pH levels. The Chick-Watson first order kinetics model was used to develop Ct values for pH levels from 6 to 11.5. A formula is provided to calculate a 100(1 - α)% upper confidence bound for these values. [ABSTRACT FROM AUTHOR]
- Subjects :
- *GIARDIA
*SEWAGE purification
*HYDROGEN ions
*DISINFECTION & disinfectants
Subjects
Details
- Language :
- English
- ISSN :
- 10934529
- Volume :
- 38
- Issue :
- 9
- Database :
- Academic Search Index
- Journal :
- Journal of Environmental Science & Health. Part A. Toxic/Hazardous Substances & Environmental Engineering
- Publication Type :
- Academic Journal
- Accession number :
- 10495016
- Full Text :
- https://doi.org/10.1081/ESE-120022892