Back to Search Start Over

Evaluation of Ground Potential Rises in a Commercial Building During a Direct Lightning Stroke Using CDEGS.

Authors :
Lee, Chien-Hsing
Chang, Cheng-Nan
Jiang, Joe-Air
Source :
IEEE Transactions on Industry Applications. Nov2015 Part 2, Vol. 51 Issue 6, p4882-4888. 7p.
Publication Year :
2015

Abstract

This paper utilizes CDEGS software to calculate the transient ground potential rise (GPR) in a commercial building, with a base of 39\ \m\ \times 13\ \m and a height of 21 m, during direct lightning strokes. The influences of soil resistivity, location of the lightning strike point, and wave shape of the lightning current on the transient GPRs of three scenarios for the building are analyzed. Such scenarios within the building include the following: 1) devices are grounded independently; 2) devices are grounded via vertical ground electrodes that are connected to each down conductor fixed on the outside of the building; and 3) devices are grounded via a ring ground electrode that is sited around the periphery of the building. The results show that the ring ground electrode provides effective lightning protection for the building under lightning and, therefore, is recommended. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00939994
Volume :
51
Issue :
6
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
111152757
Full Text :
https://doi.org/10.1109/TIA.2015.2399618