An Improved Corrective Security Constrained OPF for Meshed AC/DC Grids With Multi-Terminal VSC-HVDC.
- Source :
-
IEEE Transactions on Power Systems . Jan2016, Vol. 31 Issue 1, p485-495. 11p. - Publication Year :
- 2016
-
Abstract
- This paper presents an improved corrective security constrained optimal power flow (CSCOPF) for a meshed AC/DC power transmission network with voltage source converter based multi-terminal HVDC (VSC-MTDC) grids. The security constrains of N-1 contingencies for both AC and DC networks are fully considered in the CSCOPF problem. The corrective actions employed in this paper include not only the traditional long-term rescheduling control actions of the AC system, but also the short term post-contingency fast corrective control of multi-terminal VSC-HVDC. A hybrid method is developed to solve the improved CSCOPF problem and the effectiveness of the proposed method is evaluated and demonstrated in this paper by two example meshed AC/DC power systems. [ABSTRACT FROM AUTHOR]