Transformer Switching With Vacuum Circuit Breaker: Case Study of PV Inverter LC Filters Impact on Transient Overvoltages.

Authors :
Kuczek, T.
Florkowski, M.
Piasecki, W.
Source :
IEEE Transactions on Power Delivery. Feb2016, Vol. 31 Issue 1, p44-49. 6p.
Publication Year :
2016

Abstract

This paper presents the analysis of possible transient overvoltages that can be generated during vacuum circuit-breaker (VCB) operation at the connection point of a photovoltaic powerplant. A typical switching event that is related to the VCB concerns energization and de-energization of the unloaded transformer. However, at the typical photovoltaic powerplant, the transformer is fed by an inverter equipped with LC (or LCL) filters that are necessary for limitation of harmonics and ripple in voltage and current. From the point of view of switching operations, the inductance and capacitance of the low-voltage (LV)-side connected filter affect the natural frequency of the transformer, which is reflected by different transient system response during VCB operation. In this paper, laboratory measurement of overvoltages generated during distribution transformer switching by means of VCBs is analyzed. The impact of the LC filter connected at the LV side on the overvoltages suppression was studied. Electromagnetic Transients Program–Alternative Transients Program simulations were conducted in order to verify the possibility of transients elimination by means of the additional series-connected RL choke at the transformer medium-voltage side. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
31
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
112476023
Full Text :
https://doi.org/10.1109/TPWRD.2015.2437199