Back to Search Start Over

Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC Breakers.

Authors :
Sneath, Jeremy
Rajapakse, Athula D.
Source :
IEEE Transactions on Power Delivery. Jun2016, Vol. 31 Issue 3, p973-981. 9p.
Publication Year :
2016

Abstract

Different HVDC grid types and the respective protection options are discussed. An earthed bipole HVDC grid was modeled in PSCAD, and using simulation results, the necessity of di/dt limiting inductors to contain the rise of fault currents within the capacity of current hybrid dc breakers is demonstrated. The impact of different inductor sizes on current rise was studied. A fault detection and localization scheme using the rate of change of voltage measured at the line side of the di/dt limiting reactors is proposed. The protection system was modeled and tested under different fault types and locations. The results show that the proposed method of HVDC grid protection is feasible using the current hybrid dc breaker technology. A systematic procedure for setting the necessary protection threshold values is also demonstrated. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
31
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
115559832
Full Text :
https://doi.org/10.1109/TPWRD.2014.2364547