Back to Search Start Over

Helicopter Live-Line Work on 1000-kV<?Pub _newline ?> UHV Transmission Lines.

Authors :
Liao, Caibo
Ruan, Jiangjun
Liu, Chao
Du, Zhiye
Wen, Wu
Zhou, Taotao
Source :
IEEE Transactions on Power Delivery. Jun2016, Vol. 31 Issue 3, p982-989. 8p.
Publication Year :
2016

Abstract

Live-line work methods using helicopters in the vicinity of 1000-kV transmission lines were simulated with finite-element modeling of the electric-field distributions. The effect of the approach path of the helicopter live-line work platform toward the energized conductor was computed. Predicted electric fields on the line worker head, body, arms, and legs were compared with measured results from a single-phase ultra-high-voltage (UHV) mock-up, and with calculation results from the simulation of an extra-high-voltage (EHV) 500-kV transmission-line geometry. The UHV conductor-to-work platform discharge occurred at a distance of about 2 m, in line with standard flashover models. Additional shielding efficiency of about 4 dB is recommended for the electrically conductive clothing when working on the UHV lines in China, compared to EHV lines. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
31
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
115559851
Full Text :
https://doi.org/10.1109/TPWRD.2015.2437072