Back to Search Start Over

Symmetrical Components-Based Modified Technique for Power-Quality Disturbances Detection and Classification.

Authors :
Kumar, Raj
Singh, Bhim
Shahani, D. T.
Source :
IEEE Transactions on Industry Applications. Jul2016, Vol. 52 Issue 4, p3443-3450. 8p.
Publication Year :
2016

Abstract

This paper presents a modified approach based on symmetrical components in time domain for the detection and classification of various power-quality (PQ) disturbances. Single-phase PQ disturbance signal along with the two other ideal phases generated using phase-locked loop (PLL) is processed to find out the symmetrical components of all phases in time domain. Triggering points for PQ disturbances have been detected from the negative-sequence component of disturbance phase and have been easily classified from the signatures of the waveforms using the summation of the positive- and negative-sequence components. PQ disturbances, such as voltage sag, swell, interruption, harmonics, flicker, transients, notches, and spike present in a distribution system, have been investigated and are easily localized and segmented with this technique. Being a time-domain technique, it can be adopted for the online monitoring and assessment of the PQ disturbances. Simulated and real-time results are presented for a number of PQ disturbances to show the effectiveness of the proposed method for the PQ disturbances’ detection and classification. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
00939994
Volume :
52
Issue :
4
Database :
Academic Search Index
Journal :
IEEE Transactions on Industry Applications
Publication Type :
Academic Journal
Accession number :
116872161
Full Text :
https://doi.org/10.1109/TIA.2016.2536665