Selection criteria for oil transformer measurements to calculate the Health Index.

Authors :
Ibrahim, K.
Sharkawy, R.M.
Temraz, H.K.
Salama, M.M.A.
Source :
IEEE Transactions on Dielectrics & Electrical Insulation. Dec2016, Vol. 23 Issue 6, p3397-3404. 8p.
Publication Year :
2016

Abstract

In this paper, a study of the effect of a group of transformer measurements on Health Index (HI) calculation is presented. Different methodologies for selecting the most efficient group of diagnostic measurements used in classifying transformer HI are investigated. A Binary Cat Swarm Optimization (BCSO) technique is undertaken based on Support Vector Machines (SVM). The technique depends on selecting the optimal parameters for SVM. The effect of selecting HI classes as well as class's boundaries is also studied. The measurements of fourteen diagnostic transformer tests, including the furan analysis, dissolved gas analysis, and further oil analysis for 724 distribution transformers are studied, and the corresponding HI is calculated according to industrial standards. The model renders the best-selected group of measurements that assist in the formulation of the health index with minimum error and high confidence. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
10709878
Volume :
23
Issue :
6
Database :
Academic Search Index
Journal :
IEEE Transactions on Dielectrics & Electrical Insulation
Publication Type :
Academic Journal
Accession number :
120846939
Full Text :
https://doi.org/10.1109/TDEI.2016.006058