Back to Search Start Over

Estimation of Voltage Sags From a Limited Set of Monitors in Power Systems.

Authors :
Zambrano, Xavier
Hernandez, Araceli
Izzeddine, Mohamed
de Castro, Rosa M.
Source :
IEEE Transactions on Power Delivery. Apr2017, Vol. 32 Issue 2, p656-665. 10p.
Publication Year :
2017

Abstract

This paper proposes a probabilistic method aimed at estimating the voltage sag frequency of nonmonitored sites given the number of sags recorded by a limited set of voltage sag monitors. The proposed method is based on simulating a representative database of feasible pseudomeasurements by using probabilistic values of fault coefficient, fault impedance, fault type, and fault location. This information is processed through Bayesian filtering based on the Bayes' probabilistic theorem. This enables obtaining the most probable voltage sag index at nonmonitored busbars given the index measured at monitored busbars. This statistical estimation of sag indices at locations where there are no monitors constitutes the main contribution of this paper. This study is developed in three power systems: the IEEE 24-busbar reliability test system, the IEEE 118-busbar test system, and the transmission network of Ecuador with 357 busbars. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
32
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
122014121
Full Text :
https://doi.org/10.1109/TPWRD.2016.2594232