Back to Search Start Over

H∞ Repetitive Control Based on Active Damping with Reduced Computation Delay for LCL-Type Grid-Connected Inverters.

Authors :
Wei Jin
Yongli Li
Guangyu Sun
Lizhi Bu
Source :
Energies (19961073). May2017, Vol. 10 Issue 5, p586. 19p. 7 Diagrams, 2 Charts, 9 Graphs.
Publication Year :
2017

Abstract

In the paper, the H∞ repetitive current control scheme based on active damping along with the design method is proposed for three-phase grid-connected inverters with inductor-capacitor-inductor (LCL) filters. The control scheme aims to reduce the harmonic distortion of the output currents and achieve better efficiency. The design method introduces capacitor-current-feedback active damping into the H∞ controller design process by proposing an equivalent controlled plant. Additionally, based on the discrete model of the controlled plant with variable computation delay, the algebraic expression of the stable region for the feedback coefficient and the computation delay is obtained to avoid system instability caused by the digital control delay. Finally, the stability criterion is proposed to evaluate the stability of the discrete control system with the H∞ repetitive current control scheme. The theoretical analysis and experimental results prove that the control scheme presented in this paper not only can reject the harmonics of output currents, but is robust under the variation of the grid-impedance. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
10
Issue :
5
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
123234952
Full Text :
https://doi.org/10.3390/en10050586