Back to Search Start Over

Observation of Lightning Overvoltage in a 500 kV Switching Station.

Authors :
Sonoda, Toshio
Morii, Hiroshi
Sekioka, Shozo
Source :
IEEE Transactions on Power Delivery. Aug2017, Vol. 32 Issue 4, p1828-1834. 7p.
Publication Year :
2017

Abstract

This paper describes observation of lightning overvoltages in a 500 kV switching station at Kansai Electric Power Co., Japan. Three types of lightning overvoltages, such as back flashover, direct lightning hit to a phase conductor, and lightning-induced voltage have been observed. The lightning overvoltages due to a back flashover were lower than operation voltage of a surge arrester. The observation suggests that induced voltage caused by electromagnetic fields radiated from a lightning channel affects lightning overvoltages in a station. [ABSTRACT FROM AUTHOR]