Back to Search Start Over

A New Harmonic Reduced Three-Phase Thyristor-Controlled Reactor for Static VAr Compensators.

Authors :
Mukhopadhyay, Susovan
Maiti, Dipten
Banerji, Ambarnath
Biswas, Sujit K.
Deb, Nirmal K.
Source :
IEEE Transactions on Industrial Electronics. Sep2017, Vol. 64 Issue 9, p6898-6907. 10p.
Publication Year :
2017

Abstract

A new thyristor-controlled reactor scheme is presented in this paper, in which the total bank is split into one Δ- and one Y-connected reactor bank with the addition of a low-rating zig-zag autotransformer, instead of the conventional scheme using a Δ-connected reactor bank with a harmonic current filter. This arrangement prevents the triplen harmonics generated by the Y bank from entering into the supply system and at the same time, the combination results in cancellation of some major characteristic harmonics from the source current. Thus, without using any additional filters or phase-shifting two-winding transformer, this scheme facilitates reactive power control over a wide range and also meets the requisite harmonics standards. The scheme is simple and provides a cost-effective solution to the VAr compensation problem. Simulation and experimental results are provided to validate the proposed concept. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
02780046
Volume :
64
Issue :
9
Database :
Academic Search Index
Journal :
IEEE Transactions on Industrial Electronics
Publication Type :
Academic Journal
Accession number :
124560137
Full Text :
https://doi.org/10.1109/TIE.2017.2694409