Back to Search Start Over

Effect of refrigerant thermophysical properties on flow reversal in microchannel evaporators.

Authors :
Li, Huize
Hrnjak, Pega
Source :
International Journal of Heat & Mass Transfer. Feb2018, Vol. 117, p1135-1146. 12p.
Publication Year :
2018

Abstract

The amount and frequency of reverse flow in microchannel evaporators largely depends on the thermophysical properties of the working fluid. In this study, four refrigerants (R134a, R1234yf, R245fa and R32) are examined in the same air conditioning system operated under flash gas bypass mode with venting of reversed vapor (to provide better control of the flow). The flow rate and frequency of reversed vapor are measured for each refrigerant. It has been found that fluids with lower heat of vaporization and higher specific volume difference between vapor and liquid phase) tend to generate more reversed vapor flow. Experimental results validate qualitatively and in most cases quantitatively the mechanistic model presented in Li and Hrnjak (2017a). The validated model is used to demonstrate the effects of thermophysical properties on flow reversal for nine widely used refrigerants. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00179310
Volume :
117
Database :
Academic Search Index
Journal :
International Journal of Heat & Mass Transfer
Publication Type :
Academic Journal
Accession number :
126186040
Full Text :
https://doi.org/10.1016/j.ijheatmasstransfer.2017.10.042