An Improved Deadbeat Control for a Three-Phase Three-Line Active Power Filter With Current-Tracking Error Compensation.

Authors :
Jiang, Weidong
Ding, Xingxing
Ni, Youyuan
Wang, Jinping
Wang, Lei
Ma, Weicheng
Source :
IEEE Transactions on Power Electronics. Mar2018, Vol. 33 Issue 3, p2061-2072. 12p.
Publication Year :
2018

Abstract

An active power filter (APF) plays an important role in compensating the harmonic component of a nonlinear load current. In this paper, deadbeat control (DBC), which has high control performance and fast dynamic response, is used as a current controller for an APF. An improved DBC (Imp_DBC) is introduced to suppress the adverse effect of the current sampling error and to enhance the interference rejection capability of the control system. The characteristics of the conventional DBC and Imp_DBC are analyzed using transfer functions in the discrete-time domain. The robustness of the system is improved with the inductance variation. Specifically, aiming at the dramatic change of the harmonic component of the nonlinear load current, a current-tracking error compensation method is proposed. The phenomena of the upper co-nvex and lower concave in grid current are eliminated. Finally, the experimental setup of three-phase three-line APF is built, and the effectiveness of this method is verified by experiments. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858993
Volume :
33
Issue :
3
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Electronics
Publication Type :
Academic Journal
Accession number :
126585880
Full Text :
https://doi.org/10.1109/TPEL.2017.2693325