Bad Data Detection Using Linear WLS and Sampled Values in Digital Substations.

Authors :
Wu, Yiming
Hohn, Fabian
Nordstrom, Lars
Xiao, Yong
Zhao, Wei
Wang, Jianping
Source :
IEEE Transactions on Power Delivery. Feb2018, Vol. 33 Issue 1, p150-157. 8p.
Publication Year :
2018

Abstract

Smart Grids employ intelligent control applications that require high quality data: fast, secure, and error free. Several researchers have focused on providing techniques for low latency and secured data links for these applications. Bad data detection is however generally provided only at the central level due to limitations in legacy technologies employed in many substations. With the introduction of IEC61850 data sharing within the substation becomes more flexible and transparent allowing more sophisticated management of data quality. Hence, this paper proposes a substation level bad data detection algorithm to facilitate also these types of requirements from applications. The algorithm is based on automatically detecting the substation topology by parsing standard substation description files and online state of circuit breakers and disconnectors. By applying linear weighted least square based state estimation algorithm, bad data from failing current transformers (CT) can be detected. By conducting the verification of different types of bad data, the results show the output of bad data detection algorithm provides higher accuracy than output from both measurement and protective CT in both static and faulty situations. [ABSTRACT FROM PUBLISHER]

Details

Language :
English
ISSN :
08858977
Volume :
33
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
127499470
Full Text :
https://doi.org/10.1109/TPWRD.2017.2669110