Analysis of Air-Side Economizers in Terms of Cooling-Energy Performance in a Data Center Considering Exhaust Air Recirculation.

Authors :
Park, Seonghyun
Seo, Janghoo
Source :
Energies (19961073). Feb2018, Vol. 11 Issue 2, p444. 14p. 3 Diagrams, 5 Charts, 6 Graphs.
Publication Year :
2018

Abstract

Demand is soaring for data centers with advanced data-processing capabilities. In data centers with high-temperature information technology (IT) equipment, enormous cooling systems are operated year-round. To date, studies have aimed to improve the cooling efficiency of server-room units, but cooling-energy-consumption analysis considering the recirculation of exhaust air (EA) has not been researched to a sufficient degree. This study analyzed the cooling-energy saving effects considering the EA-recirculation and supply-air (SA)-temperature conditions when direct and indirect air-side economizers were applied to a data center in Korea. Thirteen case studies were conducted. The results showed that when the EA-recirculation ratio in the direct air-side economizer was 15%, its annual cooling-energy consumption increased by approximately 6.1% compared to the case with no recirculation. The indirect air-side economizer also exhibited an approximately 9% increase in cooling-energy consumption. On the other hand, when the SA temperature changed to 22 °C, the annual cooling-energy consumption of the direct and indirect air-side economizers decreased by approximately 67% and 55%, respectively, compared to a central chilled-water system. This indicates the importance of developing measures to prevent EA recirculation and of securing a wind path for the improvement of air-conditioning efficiency in data centers at the design stage. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
11
Issue :
2
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
128258802
Full Text :
https://doi.org/10.3390/en11020444