Back to Search Start Over

Impact of Difference of Feeder Impedances on the Performance of a Static Transfer Switch.

Authors :
Hossein Mokhtari, Alberto J.
Iravani, M. Reza
Source :
IEEE Transactions on Power Delivery. Apr2004, Vol. 19 Issue 2, p679-685. 7p.
Publication Year :
2004

Abstract

Conventionally, control system of a static transfer switch (STS) is designed based on the assumption that the STS terminal voltages are in-phase. This paper investigates the impact of phase difference of the STS terminal voltages on the STS transfer time and cross current. The phase difference is assumed to be a result of the difference of the feeder impedances. The paper shows that phase differences of even up to 4.5°, which are accompanied by up to 5% voltage drop at the STS terminal, can noticeably increase the transfer lime and the cross current magnitude. The studies are conducted on the IEEE STS-1 benchmark system using the PSCAD/EMTDC software. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
19
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
12871605
Full Text :
https://doi.org/10.1109/TPWRD.2004.825125