Back to Search Start Over

Simultaneous Network Reconfiguration with Distributed Generation Sizing and Tap Changer Adjustment for Power Loss Reduction Using Imperialist Competitive Algorithm.

Authors :
Koong, G. Ing
Aman, M. M.
Mokhlis, H.
Illias, H. A.
Jamian, J. J.
Dahalan, W. M.
Source :
Arabian Journal for Science & Engineering (Springer Science & Business Media B.V. ). Jun2018, Vol. 43 Issue 6, p2779-2792. 14p.
Publication Year :
2018

Abstract

This paper presents a simultaneous network reconfiguration with DG sizing and tap changer adjustment to minimize power loss in a distribution system. Imperialist Competitive Algorithm is used to identify the best set combination of reconfiguration, DG size and tap changer. The performance of the proposed method has been tested on 33 bus distribution system at different load levels and different scenarios of DGs location. The test results indicated an improvement of power loss reduction as compared to existing method. Furthermore, the simultaneous approach is able to produce lowest power loss than any combination of two components simultaneously. At the same time, voltage also maintains within allowable limit. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
2193567X
Volume :
43
Issue :
6
Database :
Academic Search Index
Journal :
Arabian Journal for Science & Engineering (Springer Science & Business Media B.V. )
Publication Type :
Academic Journal
Accession number :
129451595
Full Text :
https://doi.org/10.1007/s13369-017-2778-6