Back to Search Start Over

Adaptive 100% Injection-Based Generator Stator Ground Fault Protection With Real-Time Fault Location Capability.

Authors :
Safari-Shad, Nader
Franklin, Russ
Negahdari, Amir
Toliyat, Hamid A.
Source :
IEEE Transactions on Power Delivery. Oct2018, Vol. 33 Issue 5, p2364-2372. 9p.
Publication Year :
2018

Abstract

The paper presents a novel adaptive stator ground fault protection scheme with fault location capability for high-impedance grounded synchronous generators. The protection scheme uses already available neutral grounding signals in the existing subharmonic injection protection to obtain a Kalman adaptive filter (KAF) for real-time stator insulation parameter estimation. The KAF estimator yields a method of continuous tracking of stator insulation condition during healthy operations. This information is then used for real-time stator ground fault detection as well as fault location. The effectiveness of the proposed method is verified using extensive experiments performed on a lab-scale unit-connected generating station. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
33
Issue :
5
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
132099069
Full Text :
https://doi.org/10.1109/TPWRD.2018.2802423