Back to Search Start Over

Retrofitting the BCTRAN Transformer Model With Nonlinear Magnetizing Branches for the Accurate Study of Low-Frequency Deep Saturating Transients.

Authors :
Yang, Ming
Kazemi, Reza
Jazebi, Saeed
Deswal, Digvijay
de Leon, Francisco
Source :
IEEE Transactions on Power Delivery. Oct2018, Vol. 33 Issue 5, p2344-2353. 10p.
Publication Year :
2018

Abstract

In this paper, an extension to the multiwinding BCTRAN model is proposed for the study of low-frequency saturating transients in single-phase transformers. The conventional experimentally obtained BCTRAN (winding leakage) susceptance matrix is retrofitted with a previously missing experimentally obtained nonlinear (core magnetizing) model. The assembled model gives accurate results for transients in all terminals. The model parameters can be acquired from information available in the nameplate plus terminal tests without the need of detailed transformer design or construction information. Only needed are standard no-load and impedance tests plus a newly introduced saturation test. Very simple formulas are proposed to compute the parameters. Illustrative examples on how the parameters are computed are given for three transformers rated 1.8, 5, and 75 kVA. For model validation, laboratory inrush currents tests are carried out and compared with simulations using the EMTP-RV. The results show that the simulations and experimental results match very closely giving great confidence in the model correctness and parameter estimation method. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
33
Issue :
5
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
132099083
Full Text :
https://doi.org/10.1109/TPWRD.2018.2825252