Back to Search Start Over

Experimental Validation of Three-Dimension Multiconductor Cell Analysis by a 30 km Submarine Three-Core Armoured Cable.

Authors :
Benato, Roberto
Dambone Sessa, Sebastian
Forzan, Michele
Source :
IEEE Transactions on Power Delivery. Dec2018, Vol. 33 Issue 6, p2910-2919. 10p.
Publication Year :
2018

Abstract

In this paper, an experimental validation of three-dimension multiconductor cell analysis (MCA) is presented: a measurement campaign has been performed on Capri–Torre Annunziata three-core 29.5 km long submarine cable link. All the theoretical conclusions derived by the authors in a previous paper are now experimentally confirmed and the model is, therefore, validated. Based on the example in this paper, the maximum difference between MCA results and measurements is 7% on the positive sequence resistance at power frequency. A 10% difference occurs in the evaluation of positive sequence reactance. The agreement between MCA and real measurements in zero sequence impedance is very good with differences lower than 5% in real and imaginary parts. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
33
Issue :
6
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
133211722
Full Text :
https://doi.org/10.1109/TPWRD.2018.2840221