Abstract
- Expansion of high-voltage dc (HVdc) systems to multi-terminal HVdc (MT-HVdc) systems/grids considerably increases the short-circuit levels. In order to protect the emerging MT-HVdc systems/grids against fault currents, proper dc fault current limiters (FCLs) must be developed. This paper proposes an innovative high inductance solid-state dc-reactor-based FCL (HISS-DCRFCL) to be used in HVdc applications. In fact, during the HISS-DCRFCL normal operation, its inductance value is extremely low, and its value becomes considerably high during the fault period, which decreases the fault current amplitude. The proposed HISS-DCRFCL performance is analyzed by MATLAB/Simulink and the simulation results are verified and confirmed by laboratory experimental results using a scaled-down laboratory prototype setup. [ABSTRACT FROM AUTHOR]
Details
- Language :
- English
- ISSN :
- 08858977
- Volume :
- 34
- Issue :
- 2
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Power Delivery
- Publication Type :
- Academic Journal
- Accession number :
- 135536925
- Full Text :
- https://doi.org/10.1109/TPWRD.2019.2894521