Sequence Impedance Modeling and Stability Comparative Analysis of Voltage-Controlled VSGs and Current-Controlled VSGs.

Authors :
Wu, Wenhua
Chen, Yandong
Zhou, Leming
Luo, An
Zhou, Xiaoping
He, Zhixing
Yang, Ling
Xie, Zhiwei
Liu, Jinming
Zhang, Mingmin
Source :
IEEE Transactions on Industrial Electronics. Aug2019, Vol. 66 Issue 8, p6460-6472. 13p.
Publication Year :
2019

Abstract

The premise that the virtual synchronous generator (VSG) can actively support the weak grid is that the VSG can operate stably. In this paper, the small-signal sequence impedance models of the voltage-controlled VSG and the current-controlled VSG are built and the sequence impedance characteristics of these two types of VSGs are compared and analyzed. The sequence impedance of the voltage-controlled VSG, being consistent with the grid impedance characteristics, is generally inductive. By contrast, the sequence impedance of the current-controlled VSG is mainly negative impedance in the middle- and high-frequency area and the impedance amplitude is quite low. Based on the built sequence impedance models and the impedance stability criterion, the influence of the weakness of the grid on the stability of these two types of VSG grid-connected system is analyzed. The results of stability analysis show that the current-controlled VSG is prone to instability while the voltage-controlled VSG remains stable. Therefore, the voltage-controlled VSG is more suitable than the current-controlled VSG for grid-connected renewable energy generation in an ultraweak grid from the point of view of system stability. Finally, experiment results validate the stability analysis. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
02780046
Volume :
66
Issue :
8
Database :
Academic Search Index
Journal :
IEEE Transactions on Industrial Electronics
Publication Type :
Academic Journal
Accession number :
135750601
Full Text :
https://doi.org/10.1109/TIE.2018.2873523