Probabilistic risk-based management of distribution transformers by dynamic transformer rating.

Authors :
Bracale, Antonio
Carpinelli, Guido
De Falco, Pasquale
Source :
International Journal of Electrical Power & Energy Systems. Dec2019, Vol. 113, p229-243. 15p.
Publication Year :
2019

Abstract

• Risk-based procedure for managing a distribution transformer by its dynamic rating. • Formulation of an admissible risk level with an intuitive physical meaning. • Quantile regression forests to forecast transformer load and ambient temperature. • Numerical experiments are based on actual industrial data to validate the proposal. • Results are provided from energetic and economic perspectives. Electrical distribution networks are often inadequate to comply with the increasing load demand and to enable new installation of distributed energy resources. This inadequacy may result in upgrading existing transformers of in disconnecting the entire load during demand peaks, and into wasting a portion of the total renewable energy produced during favorable weather conditions. Increasing the capacity of electrical distribution network components is therefore mandatory in order to avoid these negative circumstances; however replacing lines and transformers is costly, and often the benefits are not worth the investments. Fortunately, the capacity of distribution networks can be unlocked by managing the electrical components by their dynamic ratings, allowing operating them even beyond their rated ampacity for a limited interval of time. This paper proposes a new risk-based procedure to manage distribution transformers by their dynamic rating. Probabilistic forecasts of loads and ambient temperatures are the inputs of the procedure, which are obtained in this paper from quantile regression forests. The procedure quantifies, in a probabilistic framework, the insulation thermal ageing due to the transformer (over)load in terms of the cost sustained for rewinding the transformer. The corresponding estimated risk is made available to the distribution system operator, who may therefore take a decision comparing it to an arbitrary level of risk coverage, favoring either the power delivery to customers or the reduction of the transformer ageing rate; this level is formulated in this paper having an intuitive physical meaning, thus enabling its setting also by non-expert operators. Comprehensive numerical experiments based on actual data are presented under different configurations and scenarios, in order to validate the proposal from an energetic and economic point of view. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
01420615
Volume :
113
Database :
Academic Search Index
Journal :
International Journal of Electrical Power & Energy Systems
Publication Type :
Academic Journal
Accession number :
137265734
Full Text :
https://doi.org/10.1016/j.ijepes.2019.05.048