Back to Search Start Over

Short-Circuit Model for Type-IV Wind Turbine Generators With Decoupled Sequence Control.

Authors :
Kauffmann, Thomas
Karaagac, Ulas
Kocar, Ilhan
Jensen, Simon
Farantatos, Evangelos
Haddadi, Aboutaleb
Mahseredjian, Jean
Source :
IEEE Transactions on Power Delivery. Oct2019, Vol. 34 Issue 5, p1998-2007. 10p.
Publication Year :
2019

Abstract

The power system planning and protection studies are becoming more challenging due to the rapid increase in penetration levels of converter-interfaced renewables. Type-IV wind turbine generators (WTGs) and photovoltaic panels are interfaced to the grid through a full-scale converter, and their short-circuit current contributions are mainly designated by the converter control and associated current limits. This paper proposes a new phasor domain modeling approach for the wind parks (WPs) with Type-IV WTGs, using the concept of control-based equivalent circuits. The proposed model precisely represents the detailed electromagnetic transient (EMT)-type model in steady state, and is able to account for the fault-ride-through function of the WTG control as well as its specific decoupled sequence control scheme in addition to the traditional coupled control scheme. Although the collector grid and WTGs inside the WP are represented with their aggregated models, the overall reactive power control structure of the WP is preserved by taking the central WP controller into account. The accuracy of the proposed model is validated through detailed EMT simulations. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
34
Issue :
5
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
138780402
Full Text :
https://doi.org/10.1109/TPWRD.2019.2908686