Back to Search Start Over

Optimization of the thermal environment of a small-scale data center in China.

Authors :
Meng, Xiongzhuang
Zhou, Junli
Zhang, Xuejiao
Luo, Zhiwen
Gong, Hui
Gan, Ting
Source :
Energy. Apr2020, Vol. 196, pN.PAG-N.PAG. 1p.
Publication Year :
2020

Abstract

In data centers, a large number of IT sever racks with different heat dissipation rates are arranged in multiple rows, leading to much higher per-unit heat release and therefore more uneven temperature distribution than in general buildings. This paper chooses a small-scale data center located in China to analyze the thermal environment for the operation of these critical equipments. The wind speed and temperature in the data center were measured, and a corresponding computer room model was established via computational fluid dynamics (CFD) simulation software. Based on it, the characteristics of flow field and temperature field of the data center were analyzed. The optimization methods for problem of uneven temperature distribution and chaotic air supply in the data center were proposed and verified by evaluation index. Furthermore, the return temperature index(RHI) increased from 0.918 to 0.93, the return heat index(RTI) increased from 0.222 to 0.342. • The thermal environment of a small-scale data center in Wuhan, China was measured. • The data center model was established via numerical simulation software. • The optimized schemes for the thermal environment in the data center were proposed. • Optimization of data center can provide reference for construction and operation. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
03605442
Volume :
196
Database :
Academic Search Index
Journal :
Energy
Publication Type :
Academic Journal
Accession number :
142297660
Full Text :
https://doi.org/10.1016/j.energy.2020.117080