Back to Search Start Over

Increasing the efficiency of gas turbine inlet air cooling in actual climatic conditions of Kazakhstan and Ukraine.

Authors :
Radchenko, A.
Radchenko, N.
Tsoy, A.
Portnoi, B.
Kantor, S.
Myshlyavtsev, Alexander V
Likholobov, Vladimir A
Yusha, Vladimir L
Source :
AIP Conference Proceedings. 2020, Vol. 2285 Issue 1, p1-9. 9p.
Publication Year :
2020

Abstract

The air cooling at the inlet of gas turbine unites (GTU) in operation conditions of Kazakhstan and Ukraine was analyzed. To increase the efficiency of cooling air in actual climatic conditions a two-stage deep air cooling in waste heat recovery chillers of combined type that convert the heat of exhaust gas of GTU has been proposed as a novel approach in GTU inlet air cooling. The calculations were conducted for cooling ambient air to 15 °C by absorption lithium-bromide chiller (ACh) and down to 10 °C by absorption-ejector chiller (AECh). It was shown that air cooling in AECh provides approximately 1.5 times greater annual reduction in fuel consumption compared to cooling air in ACh. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
0094243X
Volume :
2285
Issue :
1
Database :
Academic Search Index
Journal :
AIP Conference Proceedings
Publication Type :
Conference
Accession number :
147077633
Full Text :
https://doi.org/10.1063/5.0026787