Experimental comparison of R404A and R452A in refrigeration systems.

Authors :
Devecİoğlu, Atİlla G.
Oruç, Vedat
Source :
Science & Technology for the Built Environment. Jan2021, Vol. 27 Issue 1, p61-69. 9p.
Publication Year :
2021

Abstract

In this study, R404A and R452A refrigerants used in refrigeration systems were compared experimentally. The energy performance of the system was investigated for widely used evaporation temperatures (−5, 0, +5 °C) and condenser temperatures (25, 35, 45 °C). It was seen that the coefficient of performance (COP) was higher but the power consumption of the system was lower when using R452A as a substitute for R404A. When R452A was used, the COP was improved by about 3% to 8% compared to R404A. Furthermore, the cooling capacity decreased by about 2% for condenser temperatures of 25 and 35 °C, while it increased at a condenser temperature of 45 °C. The power consumption of the system was also reduced by nearly 5%. The mass flow rate of the refrigerant was lower when the system was operated with R452A. In the middle term, R452A could be a suitable alternative refrigerant for commercial refrigeration applications due to its low global warming potential (GWP) value and better energy performance compared to R404A. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
23744731
Volume :
27
Issue :
1
Database :
Academic Search Index
Journal :
Science & Technology for the Built Environment
Publication Type :
Academic Journal
Accession number :
147162700
Full Text :
https://doi.org/10.1080/23744731.2020.1796419