Back to Search Start Over

VCO‐less PLL control‐based voltage‐source converter for power quality improvement in distributed generation system.

Authors :
Giri, Ashutosh K.
Arya, Sabha Raj
Maurya, Rakesh
Babu, B. Chitti
Source :
IET Electric Power Applications (Wiley-Blackwell). Aug2019, Vol. 13 Issue 8, p1114-1124. 11p.
Publication Year :
2019

Abstract

This paper presents the voltage‐controlled oscillator (VCO) less phase‐locked loop (PLL)‐based control of voltage source converter. It is used in the distributed power generation system for improved power quality. This control extracts the fundamental component from the sensed load current using three phases to alpha–beta transformation without using VCO, unlike synchronous reference frame–PLL, where fundamental component extraction needs two transformations with the use of VCO. Owing to the absence of VCO in the proposed method, the computational burden of trigonometric operations is very less that results in a faster dynamic response under variable conditions. This characteristic makes it suitable for the distributed power generation system, where fast changes occur frequently. In this study, wind‐based distributed generation system has been taken for study, which comprises of self‐excited induction generator feeding non‐linear load with varying electrical conditions. Using the proposed control, the reactive power compensation, harmonics reduction and load balancing are carried out in the system. In addition to it, neutral current compensation is also accomplished with the help of star–delta transformer connected at the load end. The system performances are investigated under steady state as well as in transient state and results are found satisfactory. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
17518660
Volume :
13
Issue :
8
Database :
Academic Search Index
Journal :
IET Electric Power Applications (Wiley-Blackwell)
Publication Type :
Academic Journal
Accession number :
148479478
Full Text :
https://doi.org/10.1049/iet-epa.2018.5827