Abstract
- The aim of this study is the presentation of the results of an in-lab comparative study of electrical and thermal monitoring of artificially polluted, HTV-textured silicone rubber insulators, with different pollution levels. This work is a preliminary study of an in-situ monitoring of 400 kV SiR textured in a polluted environment. The results showed that the rms leakage current magnitude and pulses, and the average dissipated power depended on the pollution levels and the dry-bands formation. The discharge activity and their nature are governed by the pollution level and the voltage. A differentiation and a quantification between dry-band discharge onset and dry-band arc inception is highlighted. [ABSTRACT FROM AUTHOR]