Desarrollo de Software para especificar la puesta a tierra del Neutro de Generadores Síncronos.

Authors :
ALBEIRO TORRES DURAN, EDISON
CAICEDO DELGADO, NAYIBER GLADYS
MARLÉS SÁENZ, EDUARDO
Source :
Ingeniería y Desarrollo. jul-dic2020, Vol. 38 Issue 2, p313-337. 25p.
Publication Year :
2020

Abstract

This article studies the effects of operating a generator with an inadequate grounded conductor. Interpretation of the selection method, and calculations necessary to specify the recommended neutral grounding types, followed the IEEE Std C62.92.2™-2017 [1], IEEE Std C37.101™-2006 standards [2] and GTC-206 [3]. The conception that a software should have to facilitate the process of selection and specification of the grounding of the neutral wire of a synchronous generator is presented, which later was developed by means of a free programming environment, that allowed for the specification of all types of implementation of the recommended grounding in the aforementioned standards. As an application exercise, through the use of the developed software, compliance with these regulations could be determined in the current neutral grounding of the four generation units of the Calima Hydroelectric Power Plant. [ABSTRACT FROM AUTHOR]