Back to Search Start Over

Basic Topology, Modeling and Evaluation of a T-Type Hybrid DC Breaker for HVDC Grid.

Authors :
Zhu, Jin
Guo, Xingming
Yin, Jingyuan
Huo, Qunhai
Wei, Tongzhen
Source :
IEEE Transactions on Power Delivery. Oct2021, Vol. 36 Issue 5, p2995-3004. 10p.
Publication Year :
2021

Abstract

Hybrid circuit breaker (HCB) has shown good performance for interrupting dc fault current. However, a massive number of IGBTs in series is needed. These will lead to high costs and significant difficulty in balancing IGBT dynamic voltage. This paper proposes a bidirectional hybrid circuit breaker based on a cascaded half-bridge submodule structure to reduce the overall costs and implementation difficulty of HCB. The number of IGBTs is reduced by 50%, and the operating speed is fast enough. A model of a four-terminal modular multilevel converter (MMC) system with a proposed hybrid circuit breaker in different stages is developed to describe the fault blocking process more clearly. The performance of the proposed HCB is validated and compared with other HCB structure through both theoretical derivation and time-domain simulation. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
36
Issue :
5
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
153711152
Full Text :
https://doi.org/10.1109/TPWRD.2020.3031671