Back to Search Start Over

Surface Charge Accumulation on a Real Size Epoxy Insulator With Bouncing Metal Particle Under DC Voltage.

Authors :
Gao, Yu
Wang, Huan
Yuan, Xiaochen
Zhao, Huicun
Li, Ziyi
Source :
IEEE Transactions on Plasma Science. Jul2021, Vol. 49 Issue 7, p2166-2175. 10p.
Publication Year :
2021

Abstract

Free metal particle can affect surface charge accumulation on epoxy insulator installed in gas-insulated transmission line (GIL) or gas-insulated switchgear (GIS), which results in reduction of surface flashover voltage thus threatening the safe operation of the power equipment. This article reports on the charge accumulation behavior on a real size epoxy insulator with bouncing metal particle under DC voltage. A coaxial electrode system was designed for the test under −30 kV, a metal particle-launching system was employed to inject the bouncing linear particle to the insulator surface. The charge distribution was measured by a Kelvin-type probe, and the influence of the particle on the charge accumulation was analyzed with the help of electric field simulation. The results showed that there were mainly two moving patterns of the bouncing particle: the charges were accumulated with speckle shape and the charged particle that hit the edge of electrode had more remarkable influence on the charge accumulation than other particles. It is suggested that the charge distribution feature is dependent upon the collision point and the trajectory of the bouncing particle. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
00933813
Volume :
49
Issue :
7
Database :
Academic Search Index
Journal :
IEEE Transactions on Plasma Science
Publication Type :
Academic Journal
Accession number :
153764100
Full Text :
https://doi.org/10.1109/TPS.2021.3089504