Effect of Different Plenum-Chamber Coefficients on the Frosting of Air-Cooler.

Authors :
Liu, Bin
Shi, Shengqiang
Liu, Yongshan
Bennacer, Rachid
Chen, Aiqiang
Theodorakis, Panagiotis E.
Source :
Energies (19961073). Jan2022, Vol. 15 Issue 2, p422. 1p.
Publication Year :
2022

Abstract

The performance of the air-cooler in refrigeration systems plays a key role in their energy efficiency. Here, the plenum-chamber coefficient was defined to investigate a possible way of enhancing the refrigeration coefficient that reflects the efficiency of the system. To investigate the influence of the plenum-chamber coefficient on the frosting and the cooling system of the air-cooler, three plenum-chamber coefficients (0.74, 0.97, 1.2) were studied under two different relative humidities. The temperature decreasing curve of the environmental chamber, the velocity distribution of the air-cooler, and the frost accumulation under and on the air-cooler were analyzed. We find that the homogeneity of the velocity distribution of the air-cooler and the frost accumulation increase with a growing plenum-chamber coefficient, while the frost accumulation on the fin will first increase and then decrease with the increase in the plenum-chamber coefficient. In general, frosting is more present when the plenum-chamber coefficient is 0.97. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
15
Issue :
2
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
154816066
Full Text :
https://doi.org/10.3390/en15020422