Back to Search Start Over

Sub-Synchronous Ferroresonance Causes Catastrophic Failure of a Line Shunt Reactor – A Post Mortem Investigation.

Authors :
Nagpal, Mukesh
Jiao, Zhixian
Manuel, Ska-Hiish
Martinich, Terry
Merriman, Steve
Sydor, Dave
Source :
IEEE Transactions on Power Delivery. Feb2022, Vol. 37 Issue 1, p374-382. 9p.
Publication Year :
2022

Abstract

On March 31, 2019, a 500 kV air-core, shunt reactor at a large generating station in BC Hydro was damaged shortly after four unit transformers were simultaneously energized from a 500 kV series and shunt compensated line source. Forensic investigations revealed that the controlled switching system, controlling the instant at which each breaker phase closes during energization to minimize inrush current, had failed. Uncontrolled closing led to under-damped, high-magnitude and sub-synchronous currents. Protection tripped and isolated the four transformers, followed shortly by shunt reactor protection tripping. Before the reactor could be isolated by circuit breakers, a damaging internal fault developed. This paper presents forensic investigation describing sequence of events leading up to reactor damage and shares the lessons learned with the peer utilities having similar installations.    [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
37
Issue :
1
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
154862044
Full Text :
https://doi.org/10.1109/TPWRD.2021.3060386