Oil Conductivity Estimation of Transformer Insulation by Switching Impulse Application.
- Source :
-
IEEE Transactions on Dielectrics & Electrical Insulation . Apr2022, Vol. 29 Issue 2, p420-427. 8p. - Publication Year :
- 2022
-
Abstract
- This article discusses an advanced method for estimating dc conductivity of oil using parameters evaluated under switching impulse voltage application. Firstly, the effectiveness of switching impulse application for assessing the condition of oil–paper insulation is investigated. Thereafter, the evaluated parameters under switching impulse voltage are fitted by Havriliak and Negami (HN) model for estimating the oil conductivity. The method is applied on oil-impregnated pressboards containing different moistures and a distribution transformer for experimental investigation. Moreover, the limitations of the proposed method are also discussed in this article. [ABSTRACT FROM AUTHOR]
- Subjects :
- *TRANSFORMER insulation
*POWER transformers
Subjects
Details
- Language :
- English
- ISSN :
- 10709878
- Volume :
- 29
- Issue :
- 2
- Database :
- Academic Search Index
- Journal :
- IEEE Transactions on Dielectrics & Electrical Insulation
- Publication Type :
- Academic Journal
- Accession number :
- 156719038
- Full Text :
- https://doi.org/10.1109/TDEI.2022.3157925