Back to Search Start Over

High Voltage Winding Internal Electric Field Shielding Structure for Medium Voltage High Frequency Transformers.

Authors :
Lu, Rui
Yu, Jianxiong
Li, Chengmin
Li, Chushan
Li, Wuhua
He, Xiangning
Source :
IEEE Transactions on Power Electronics. Oct2022, Vol. 37 Issue 10, p11469-11474. 6p.
Publication Year :
2022

Abstract

In this letter, an internal electric field shielding layer for high voltage winding of medium voltage high frequency transformer used in a modular cascaded medium voltage solid state transformer is proposed. Without breaking the litz wire insulation layer, the high electric field is effectively shielded by a semiconducting layer and an unclosed copper foil spiral, which are electrically connected together. Not only the electric field in the main wall insulation is uniformed but also the peak value of the internal field is greatly reduced, which will help to achieve lower partial discharge and higher insulation reliability. With this structure, the difficulties of pouring process and electric field estimation for the litz wire winding are both avoid. Finally, a no partial discharge 100 kW medium voltage high frequency transformer prototype with 75 kV base insulation level is built and verified with the insulation tests. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858993
Volume :
37
Issue :
10
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Electronics
Publication Type :
Academic Journal
Accession number :
157619053
Full Text :
https://doi.org/10.1109/TPEL.2022.3169019