Back to Search Start Over

Effective Length of Counterpoise Wire Under Lightning Current.

Authors :
Jinliang He
Yanqing Gao
Rong Zeng
Jun Zou
Xidong Liang
Bo Zhang
Jaebok Lee
Sughun Chang
Source :
IEEE Transactions on Power Delivery. Apr2005 Part 2, Vol. 20 Issue 2, p1585-1591. 7p.
Publication Year :
2005

Abstract

In a high soil resistivity area, counterpoise wires are applied to decrease the grounding resistance of tower grounding devices. If the conductor of counterpoise wire is very long, although the power frequency grounding resistance of the tower grounding device ii decreased, the lightning protection performance of the transmission line is still not good. The influences of the length of grounding electrodes on the lightning transient characteristic were analyzed. The dynamic and nonlinear effect of soil ionization around the grounding electrode was considered in the analysis model of transient characteristics for the grounding electrodes under lightning impulse. The counterpoise wire has an effective length when lightning passes through it. When the length of a grounding electrode exceeds the effective length, the grounding conductor will not be utilized effectively. The simulating experiments were performed to analyze influences of the length of the counterpoise wire on the impulse characteristics. The formulae to calculate the impulse effective lengths of counterpoise wires were proposed. The model proposed in the paper has been validated by comparing the numerical results with experimental tests. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
08858977
Volume :
20
Issue :
2
Database :
Academic Search Index
Journal :
IEEE Transactions on Power Delivery
Publication Type :
Academic Journal
Accession number :
16680257
Full Text :
https://doi.org/10.1109/TPWRD.2004.838457