Back to Search Start Over

Optimal Location and Size of Static Var Compensators (SVC) to Enhance the Voltage Profile on the Main Interconnected System in Oman.

Authors :
Al-Saidi, Marwa
Al-Badi, Abdullah
Onen, Ahmet
Elhaffar, Abdelsalam
Source :
Energies (19961073). Oct2023, Vol. 16 Issue 19, p6802. 15p.
Publication Year :
2023

Abstract

This study aimed to optimize the incorporation of static var compensators (SVCs) into Oman's main interconnected system (MIS) using real 2023 MIS data. Leveraging the particle swarm optimization (PSO) algorithm within MATLAB, substantial enhancements were achieved in voltage profiles, with associated losses reducing by roughly 2%. A multi-objective strategy effectively managed costs while preserving improved voltage profiles and controlled losses. Validation through DigSILENT showcased the dynamic advantages of optimal SVC placement through consistently elevating voltage profiles and mitigating losses, notably within the Muscat region. Analyses encompassing harmonics, transient stability, and load distribution indicated that harmonics remained within acceptable thresholds, and overall system stability was enhanced. Optimal SVC deployment expedited the attainment of steady-state conditions, as illustrated via the QV curve, demonstrating increased stability as the buses loaded from 18% to 96%. These findings underscore the robust and efficient nature of SVC integration as a viable solution within Oman's MIS system, addressing voltage profile enhancement, loss minimization, and fortified system stability. [ABSTRACT FROM AUTHOR]

Details

Language :
English
ISSN :
19961073
Volume :
16
Issue :
19
Database :
Academic Search Index
Journal :
Energies (19961073)
Publication Type :
Academic Journal
Accession number :
172983169
Full Text :
https://doi.org/10.3390/en16196802