地板下送风数据中心冷通道导流的结构研究.

Authors :
许陆顺
张忠斌
宋 平
巩 莉
Source :
Journal of Xi'an Polytechnic University. 2023, Vol. 37 Issue 5, p53-60. 8p.
Publication Year :
2023

Abstract

In response to the issue of suboptimal thermal performance in traditional data centers, four distinct airflow management structures, namely, composite, linear, convex, and concave diversion plates, were proposed. Utilizing Airpak 3.0, numerical simulations were conducted on five different data centers, including the original configuration of the computer room air conditioner (CRAC). The objective was to assess the impact of various airflow management structures on the thermal performance of data centers, with experimental validation of the model. The findings demonstrate that these airflow management structures significantly enhance the thermal performance of data centers. Among them, the composite diversion plate yielded moderate improvements, the convex diversion plate effectively optimized velocity distribution, although with limitations in temperature optimization, and the concave diversion plate exhibited non-uniform temperature distribution. Overall, considering all factors, the linear diversion plate proved to be the most effective. [ABSTRACT FROM AUTHOR]